ELE06-03698
| Final | 10/5/2006 | 10/5/2006 | 10/5/2006 4:25:23 PM | P | CANC |
|
|
Brent; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr, no address, no job id sticker
|
ELE06-03545
| Electrical Rough-In | 10/4/2006 | 10/5/2006 | 10/5/2006 4:02:46 PM | P | PART |
|
|
clyde Note: upstairs ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles upstairs only ok to cover
|
ELE06-03542
| Electrical Rough-In | 10/5/2006 | 10/5/2006 | 10/5/2006 3:22:33 PM | P | PASS |
|
|
inspection for concrete incased electrode.; Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok to cover concrete encased electrode
|
ELE06-03296
| Permanent Service | 10/5/2006 | 10/5/2006 | 10/5/2006 2:35:14 PM | P | CANC |
|
|
thank you!; Phone #: ###-#### Internet Inspection Request from: Zane Robertson called contr, wrong type inspection request, see ri
|
ELE06-03296
| Electrical Rough-In | 10/5/2006 | 10/5/2006 | 10/5/2006 2:34:27 PM | P | FAIL |
|
|
thank you!; Phone #: ###-#### Internet Inspection Request from: Zane Robertson called contr, said to clean out around gec and recall for inspection to pour, said that 4" conduit into 4" deep can would not work because cutting down locknut voids ul listing and that bushing will not fit either. Told about either ground both disconnects or locate in meter can.
|
ELE06-03596
| Permanent Service | 10/5/2006 | 10/5/2006 | 10/5/2006 1:04:14 PM | P | PASS |
|
|
Steve; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s u/g rec ok
|
ELE06-03690
| Rough-In Permanent Service | 10/4/2006 | 10/5/2006 | 10/5/2006 10:41:33 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ric ok , p/s u/g n ok
|
ELE05-02260
| ELE-Aging Inspection | 10/5/2006 | 10/5/2006 | 10/5/2006 10:22:53 AM | | DONE |
|
|
called contr, they will call for final, apparently motors relocated and rewired
|
ELE05-04290
| ELE-Aging Inspection | 10/5/2006 | 10/5/2006 | 10/5/2006 10:21:42 AM | | NR |
|
|
not ready yet
|
ELE05-01707
| ELE-Aging Inspection | 10/5/2006 | 10/5/2006 | 10/5/2006 10:11:50 AM | | DONE |
|
|
called elect asked to call for final, it is supposed to be main bldg of health and welfare
|
ELE06-01612
| Electrical Rough-In | 10/5/2006 | 10/5/2006 | 10/5/2006 9:38:28 AM | A | FAIL |
|
|
called elect, BCC no nm cable shall be used in commercial buildings, nec 358.26 there shall not be more than 360 degree bends in emt to rooftops, left corr notice
|
ELE06-03484
| Electrical Rough-In | 10/4/2006 | 10/5/2006 | 10/5/2006 9:22:46 AM | A | PASS |
|
|
Walls Rough In ; Phone #: ###-#### Internet Inspection Request from: Kristopher wilson walls only ok to cover
|
ELE06-02311
| Electrical Rough-In | 10/4/2006 | 10/5/2006 | 10/5/2006 8:45:54 AM | A | FAIL |
|
|
Underground inspection, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters called, left message, BCC all u/g shall be inspected before cover, nec 300.5 rnc shall be minimum 24" under parking and drive areas
|
ELE06-03615
| Permanent Service | 10/4/2006 | 10/5/2006 | 10/4/2006 3:34:07 PM | A | PASS |
|
|
mark Note: please call 1/2 hr prior; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g rec ok
|