Inspections for the day of: Thursday, October 5, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03698 Final10/5/200610/5/200610/5/2006 4:25:23 PMPCANC
Brent; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr, no address, no job id sticker
ELE06-03545 Electrical Rough-In10/4/200610/5/200610/5/2006 4:02:46 PMPPART
clyde Note: upstairs ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles upstairs only ok to cover
ELE06-03542 Electrical Rough-In10/5/200610/5/200610/5/2006 3:22:33 PMPPASS
inspection for concrete incased electrode.; Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok to cover concrete encased electrode
ELE06-03296 Permanent Service10/5/200610/5/200610/5/2006 2:35:14 PMPCANC
thank you!; Phone #: ###-#### Internet Inspection Request from: Zane Robertson called contr, wrong type inspection request, see ri
ELE06-03296 Electrical Rough-In10/5/200610/5/200610/5/2006 2:34:27 PMPFAIL
thank you!; Phone #: ###-#### Internet Inspection Request from: Zane Robertson called contr, said to clean out around gec and recall for inspection to pour, said that 4" conduit into 4" deep can would not work because cutting down locknut voids ul listing and that bushing will not fit either. Told about either ground both disconnects or locate in meter can.
ELE06-03596 Permanent Service10/5/200610/5/200610/5/2006 1:04:14 PMPPASS
Steve; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s u/g rec ok
ELE06-03690 Rough-In Permanent Service10/4/200610/5/200610/5/2006 10:41:33 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ric ok , p/s u/g n ok
ELE05-02260 ELE-Aging Inspection10/5/200610/5/200610/5/2006 10:22:53 AM DONE
called contr, they will call for final, apparently motors relocated and rewired
ELE05-04290 ELE-Aging Inspection10/5/200610/5/200610/5/2006 10:21:42 AM NR
not ready yet
ELE05-01707 ELE-Aging Inspection10/5/200610/5/200610/5/2006 10:11:50 AM DONE
called elect asked to call for final, it is supposed to be main bldg of health and welfare
ELE06-01612 Electrical Rough-In10/5/200610/5/200610/5/2006 9:38:28 AMAFAIL
called elect, BCC no nm cable shall be used in commercial buildings, nec 358.26 there shall not be more than 360 degree bends in emt to rooftops, left corr notice
ELE06-03484 Electrical Rough-In10/4/200610/5/200610/5/2006 9:22:46 AMAPASS
Walls Rough In ; Phone #: ###-#### Internet Inspection Request from: Kristopher wilson walls only ok to cover
ELE06-02311 Electrical Rough-In10/4/200610/5/200610/5/2006 8:45:54 AMAFAIL
Underground inspection, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters called, left message, BCC all u/g shall be inspected before cover, nec 300.5 rnc shall be minimum 24" under parking and drive areas
ELE06-03615 Permanent Service10/4/200610/5/200610/4/2006 3:34:07 PMAPASS
mark Note: please call 1/2 hr prior; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g rec ok