Inspections for the day of: Friday, October 5, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00821 INSP-Sprinkler Rough-in10/4/200710/5/200710/5/2007 10:29:13 PMAFAIL
The hood suppression system is not interconnected to the fire alarm panel (FACP is not functional at this time), wiring to the microswitch is not approved as installed, need to provide signage at the water supply isolation valve, no trip test completed at this time due to jobstie conditions, permit cannot be finaled or cooking equipment allowed to be used at this time.
FIR07-00321 FIR-Aging Inspection10/5/200710/5/200710/5/2007 3:10:32 PM DEFR
wip
FIR07-00787 INSP-Final Inspection10/5/200710/5/200710/5/2007 3:10:11 PMPPASS
Fire sprinkler work passed field inspection, permit finaled.
BLD07-02395 FIRE-Final Inspection10/5/200710/5/200710/5/2007 2:42:17 PMPPASS
Fire life safety passed.
FIR07-00796 INSP-Sprinkler Rough-in/Hydro10/5/200710/5/200710/5/2007 2:40:34 PMPPART
OH install is acceptable as noted, need flexible coupling at the riser masonry wall, also need to call in project related permit for inspection, hydrostatic test completed although not necessary as project is less than 20 heads total.
FIR07-00425 INSP-Sprinkler Rough-in/Hydro10/4/200710/5/200710/5/2007 2:12:26 PMAFAIL
OH hydrostatic test for the 3rd floor failed due to pressure loss at the guage.
FIR07-00425 INSP-Sprinkler Rough-in/Hydro10/5/200710/5/200710/5/2007 2:11:32 PMPDEFR
Duplicate inspection request.
BLD07-01051 FIRE-Final Inspection10/4/200710/5/200710/5/2007 2:10:54 PMAPASS
Fire life safety is satisfactory, noted the manual thumbturn at the main entry/exit shall be removed prior to structural final inspection.
FIR07-00754 INSP-Final Inspection10/3/200710/5/200710/5/2007 1:03:16 PMAPASS
Fire alarm work passed inspection, as-built plans accepted.
FIR07-00755 INSP-Sprinkler Rough-in/Hydro10/4/200710/5/200710/5/2007 10:48:55 AMAPART
Pneumatic testing for the preaction system passed.