Inspections for the day of: Monday, October 5, 2009.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00584 INSP-Alarm Testing10/2/200910/5/200910/5/2009 3:14:53 PMPFAIL
Testing will need to be redone due to the monitoring account not being set up.
BLD09-01367 FIRE-Final Inspection10/2/200910/5/200910/5/2009 3:09:57 PMAFAIL
This inspection was an ok for partial use of the east side dressing rooms.
FIR09-00581 INSP-Sprinkler Rough-in10/5/200910/5/200910/5/2009 2:47:27 PMPPASS
The underground supply piping is ok to cover.
FIR09-00490 INSP-Final Inspection10/5/200910/5/200910/5/2009 2:46:25 PMPPASS
Permit finaled. Upright protection has been provided in the combustible concealed space as requested.
BLD07-02085 FIRE-Final Inspection10/1/200910/5/200910/5/2009 2:45:30 PMPFAIL
The project related fire sprinkler and fire alarm permits need to be finaled, both of the horizontal sliding doors need to be adjusted so that they easily open manually, the atrium smoke evacuation system needs to be addressed, the exit discharge lighting needs to be removed from control by the photocells and electrical super vision of the horizontal sliding doors needs to be addressed. All of the exit signs, emergency lights and exit discharge lights need to be inspected for placement and tested for functionality after the generator switch over has been repaired. Also need to verify that the relocation of the emergency generator is ok with plan review.
BLD07-02082 FIRE-Final Inspection10/1/200910/5/200910/5/2009 2:45:05 PMPFAIL
The project related fire sprinkler and fire alarm permits need to be finaled, both of the horizontal sliding doors need to be adjusted so that they easily open manually, the atrium smoke evacuation system needs to be addressed, the exit discharge lighting needs to be removed from control by the photocells and electrical super vision of the horizontal sliding doors needs to be addressed. All of the exit signs, emergency lights and exit discharge lights need to be inspected for placement and tested for functionality after the generator switch over has been repaired. Also need to verify that the relocation of the emergency generator is ok with plan review.
BLD07-02083 FIRE-Final Inspection10/1/200910/5/200910/5/2009 2:44:44 PMPFAIL
The project related fire sprinkler and fire alarm permits need to be finaled, both of the horizontal sliding doors need to be adjusted so that they easily open manually, the atrium smoke evacuation system needs to be addressed, the exit discharge lighting needs to be removed from control by the photocells and electrical super vision of the horizontal sliding doors needs to be addressed. All of the exit signs, emergency lights and exit discharge lights need to be inspected for placement and tested for functionality after the generator switch over has been repaired. Also need to verify that the relocation of the emergency generator is ok with plan review.
FIR08-00830 INSP-Final Inspection10/2/200910/5/200910/5/2009 2:38:59 PMAFAIL
The issue with the atrium sprinkler protection is waiting to be resolved. The backflow preventor that is installed is not what was submitted on and signage needs to be provided for the control valves. Per Lonnie the outside alarm bell will be changed out and the signage provided on it as well.
FIR09-00482 INSP-Sprinkler Rough-in10/2/200910/5/200910/5/2009 9:13:53 AMAPASS
The new PIV piping can be covered.
BLD09-01304 FIRE-Final Inspection10/2/200910/5/200910/5/2009 6:06:27 AMAPASS
Life safety passed.
BLD09-01303 FIRE-Final Inspection10/2/200910/5/200910/5/2009 6:05:37 AMAPASS
life safety passed.
FIR09-00545 INSP-Final Inspection10/2/200910/5/200910/5/2009 5:57:09 AMAPASS
Permit finaled