Inspections for the day of: Friday, October 5, 2012.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02269 Electrical Rough-In10/5/201210/5/201210/5/2012 4:08:56 PMPPASS
Ceiling cover. Thanks. Phone #: ###-#### >> Inspection requested via web by Chad McKibben rough-in ok cover ceiling grid
ELE12-01710 Electrical Rough-In10/5/201210/5/201210/5/2012 3:08:07 PMPPASS
Contact: Jon Starke underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in cover underground (duct bank) under north alley
ELE12-01885 Electrical Rough-In10/5/201210/5/201210/5/2012 2:38:21 PMPPASS
mike Phone #: ###-#### corrections done rough-in ok cover walls and hard lid ceiling, shower-break room near service depart.
ELE12-02447 Permanent Service10/5/201210/5/201210/5/2012 2:09:37 PMPPASS
Justin Phone #: ###-#### p/s o/h rec ok
ELE12-01903 Final10/5/201210/5/201210/5/2012 1:19:57 PMPPASS
Garage code is 6288 enter Phone #: ###-#### >> Inspection requested via web by Zane Robertson final ok
ELE12-02457 Electrical Rough-In10/5/201210/5/201210/5/2012 12:54:31 PMPPASS
John Micka-Behind the block building at the cell tower off the dirt road Phone #: ###-#### rough-in ok cover under ground trenches
ELE12-02476 Permanent Service10/4/201210/5/201210/5/2012 10:46:42 AMAFAIL
This house has been off for a yr, need to reenergize. Lockbox code=12468. Jeff Creek ###-####. Phone #: ###-#### >> Inspection requested via web by Andrea Creek Service entrance conduit requires strap within 3 ft. of meter, conductors #4 and larger require bushing in meter main, sub-panel requires all KOs to be filled, branch circuit conductor shall enter through listed connector Locate service electrode grounding conductor connection or drive two new ground rods
ELE12-02269 Electrical Rough-In10/4/201210/5/201210/5/2012 10:01:03 AMAFAIL
Tyson is the contact. Cover for ceiling. He made corrections to the inspection that failed on 10/4. Thanks. Phone #: ###-#### >> Inspection requested via web by Chad McKibben Corrections not completed on reinspection
ELE12-02473 Electrical Rough-In10/4/201210/5/201210/5/2012 9:28:57 AMAPASS
hot tub Phone #: ###-#### >> Inspection requested via web by PAT MILLER rough-in ok call for final after replacement of receptacle
ELE12-02300 Electrical Rough-In10/4/201210/5/201210/5/2012 8:53:45 AMAPASS
floor heat Phone #: ###-#### >> Inspection requested via web by PAT MILLER rough-in ok cover UL listed floor heat mat
ELE12-02287 Final10/4/201210/5/201210/5/2012 8:41:19 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn final ok