FIR03-00066
| FIR-Aging Inspection | 10/5/2015 | 10/5/2015 | 10/13/2015 1:36:04 PM | | PASS |
|
|
permit finaled
|
FIR15-00177
| INSP-Final Inspection | 10/5/2015 | 10/5/2015 | 10/5/2015 3:00:35 PM | P | FAIL |
|
|
Tried to retest the electric alarm bell and found the the backflow preventor appears to be "cycling" and not allowing the flow switch to activate.
|
FIR15-00640
| INSP-Sprinkler Rough-in/Hydro | 10/2/2015 | 10/5/2015 | 10/5/2015 2:18:28 PM | P | CANC |
|
|
Contact - Matt Robison - ###-#### Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR15-00655
| INSP-Sprinkler Rough-in/Hydro | 10/2/2015 | 10/5/2015 | 10/5/2015 2:17:56 PM | P | CANC |
|
|
Contact - Matt Robison - ###-#### Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR15-00303
| INSP-Sprinkler Rough-in/Hydro | 10/5/2015 | 10/5/2015 | 10/5/2015 2:17:28 PM | P | PASS |
|
|
Overhead hydro test passed.
|
BLD15-01632
| FIRE-Final Inspection | 10/2/2015 | 10/5/2015 | 10/5/2015 2:17:05 PM | A | FAIL |
|
|
Need insulation attached in more locations in Mech Room 125, exit signs and emergency lights still did not get repaired and there is still the possible issue with the vanilla finish permit
|
FIR15-00640
| INSP-Supply line flush | 10/2/2015 | 10/5/2015 | 10/5/2015 11:27:49 AM | A | PASS |
|
|
Underground flush passed
|
FIR15-00655
| INSP-Supply line flush | 10/2/2015 | 10/5/2015 | 10/5/2015 11:27:23 AM | A | PASS |
|
|
underground flush passed
|
FIR15-00656
| INSP-Supply line flush | 10/2/2015 | 10/5/2015 | 10/5/2015 11:25:25 AM | A | PASS |
|
|
Underground flush passed
|
FIR15-00215
| INSP-Final Inspection | 10/2/2015 | 10/5/2015 | 10/5/2015 11:17:46 AM | P | PASS |
|
|
Permit finaled
|
FIR15-00286
| INSP-Final Inspection | 10/2/2015 | 10/5/2015 | 10/5/2015 11:05:58 AM | P | PASS |
|
|
permit finaled
|
FIR15-00216
| INSP-Final Inspection | 10/2/2015 | 10/5/2015 | 10/5/2015 10:58:24 AM | P | PASS |
|
|
permit finaled
|
FIR15-00287
| INSP-Final Inspection | 10/2/2015 | 10/5/2015 | 10/5/2015 10:55:56 AM | P | PASS |
|
|
Permit finaled
|
BLD14-03492
| FIRE-Final Inspection | 10/2/2015 | 10/5/2015 | 10/5/2015 9:34:20 AM | A | FAIL |
|
|
Need shell core finaled, need hardware between office and warehouse either reversed or changed to passage
|
BLD14-03491
| FIRE-Final Inspection | 10/2/2015 | 10/5/2015 | 10/5/2015 9:33:48 AM | A | FAIL |
|
|
Need shell core finaled, need hardware between office and warehouse either reversed or changed to passage
|
BLD14-03490
| FIRE-Final Inspection | 10/2/2015 | 10/5/2015 | 10/5/2015 9:33:09 AM | A | FAIL |
|
|
Need shell core finaled, need hardware between office and warehouse either reversed or changed to passage, need exit discharge light at north end of building repaired.
|
BLD14-03468
| FIRE-Final Inspection | 10/2/2015 | 10/5/2015 | 10/5/2015 9:31:44 AM | A | FAIL |
|
|
Need all small documents, need new location of the fire hydrant approved, need exit discharge light on north end of building repaired. Need the project related fire alarm and fire sprinkler permits finaled.
|
FIR15-00177
| INSP-Final Inspection | 10/1/2015 | 10/5/2015 | 10/5/2015 9:28:07 AM | P | FAIL |
|
|
Need test papers and tags for riser, bell did not work. Forward flush passed.
|
FIR15-00250
| INSP-Final Inspection | 10/4/2015 | 10/5/2015 | 10/5/2015 9:26:01 AM | A | FAIL |
|
|
Need correct responding address, need as-builts submitted to Lee, outside electric bell did not function, phone lines for fire alarm control panel need to be installed correctly, need map at the fire alarm control panel. All other items tested ok.
|
FIR15-00656
| INSP-Sprinkler Rough-in/Hydro | 10/2/2015 | 10/5/2015 | 10/5/2015 9:23:00 AM | P | PASS |
|
|
Rough-in passed. Piping can not be covered until a tenting inspection has passed.
|
FIR15-00657
| INSP-Sprinkler Rough-in/Hydro | 10/2/2015 | 10/5/2015 | 10/2/2015 2:35:23 PM | P | CANC |
|
|
Contact is Matt Robison- ###-#### - Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR15-00657
| INSP-Supply line flush | 10/2/2015 | 10/5/2015 | 10/2/2015 2:35:20 PM | A | CANC |
|
|
Contact is Matt Robison- ###-#### - Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|