Inspections for the day of: Monday, October 5, 2015.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00724 INSP-Final Inspection10/1/201510/5/201510/5/2015 3:35:55 PMAPART
Test of fire alarm system for wing E - all floors including a portion of the parking garage system, includingt test of all in-room smoke detectors, corridor SDs, manual pulls, SFDs, waterflows and tampers. All tested OK, except for the dry-pipe attic sprinkler system which will have to be retested after an accelerator device is added to this system.
NOTE: Wings F & G not ready for testing yet, although there are a few devices in bldg. F that will have to be made functional as they are located in the wing E TCO area. Also, elevator testing for this wing not performed yet - the state is scheduled to conduct their test tomorrow.
FIR14-00708 INSP-Alarm Testing10/5/201510/5/201510/5/2015 3:29:41 PMPPART
Test of wet-pipe systems for wings E, F & G, including all fire alarm interface testing - waterflows and tamper supervisory signals.
All floors etsted OK (within 60 seconds). The trip test of the dry pipe valve protecting the attics of these wings did not flow water within the 60 seconds time limit, therefore an accelerator will have to be installed on thsi system.