FIR04-00548
| INSP-Sprinkler Rough-in/Hydro | 10/6/2004 | 10/6/2004 | 10/6/2004 3:26:49 PM | P | CANC |
|
|
Jonathan is our foreman on site. Please call prior to arrival. We need this to be the last inspection of the day. We may not be ready till morning. So please call Jonathan before arriving. Thank you.; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
|
BLD04-00384
| FIRE-Final Inspection | 10/5/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | A | FAIL |
|
|
Need sprinkler protection in corridor and the building plans show a 1 1/2 hour fire door which is not installed 10/6/2004 12:08:30 PM
|
BLD04-01672
| FIRE-Final Inspection | 10/5/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | A | PASS |
|
|
Life safety finaled 10/6/2004 11:05:48 AM
|
FIR04-00581
| INSP-Final Inspection | 10/6/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | A | PASS |
|
|
Fire sprinklers finaled
|
FIR04-00537
| INSP-Final Inspection | 10/6/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled 10/6/2004 3:25:32 PM
|
FIR04-00610
| INSP-Sprinkler Rough-in | 10/6/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | P | PART |
|
|
Sprinkler supply is c900 blue brute with MJ 90 and ductile rise up to flange. 10/6/2004 12:06:19 PM
|
FIR04-00478
| INSP-Final Inspection | 10/6/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | P | PASS |
|
|
fire alarm finaled
|
FIR04-00256
| INSP-Final Inspection | 10/5/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | P | NR |
|
|
Existing smoke detectors do not release doors, infact they don't send any signals to the fire alarm panel 10/6/2004 2:03:44 PM
|
FIR04-00478
| INSP-Final Inspection | 10/5/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 10/6/2004 2:00:58 PM
|
FIR04-00594
| INSP-Final Inspection | 10/6/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | P | FAIL |
|
|
Provide 14awg wire instead of 16awg as per plans. Provide verification on duct detector shutdown (plans). Plans show dual phone lines but there are no phone lines. There are sprinklers in the kitchen but actual head count is not known for possible sprinkler system monitoring 10/6/2004 3:17:38 PM
|
FIR04-00548
| INSP-Sprinkler Rough-in/Hydro | 10/6/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | P | CANC |
|
|
Contractor is not ready 10/6/2004 4:02:38 PM
|
FIR04-00573
| INSP-Sprinkler Rough-in/Hydro | 10/6/2004 | 10/6/2004 | 10/6/2004 12:00:00 AM | P | PART |
|
|
Hardlid areas as marked on plans are ok to cover 10/6/2004 3:26:50 PM
|