Inspections for the day of: Wednesday, October 6, 2004.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00548 INSP-Sprinkler Rough-in/Hydro10/6/200410/6/200410/6/2004 3:26:49 PMPCANC
Jonathan is our foreman on site. Please call prior to arrival. We need this to be the last inspection of the day. We may not be ready till morning. So please call Jonathan before arriving. Thank you.; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
BLD04-00384 FIRE-Final Inspection10/5/200410/6/200410/6/2004 12:00:00 AMAFAIL
Need sprinkler protection in corridor and the building plans show a 1 1/2 hour fire door which is not installed 10/6/2004 12:08:30 PM
BLD04-01672 FIRE-Final Inspection10/5/200410/6/200410/6/2004 12:00:00 AMAPASS
Life safety finaled 10/6/2004 11:05:48 AM
FIR04-00581 INSP-Final Inspection10/6/200410/6/200410/6/2004 12:00:00 AMAPASS
Fire sprinklers finaled
FIR04-00537 INSP-Final Inspection10/6/200410/6/200410/6/2004 12:00:00 AMPPASS
Fire sprinkler finaled 10/6/2004 3:25:32 PM
FIR04-00610 INSP-Sprinkler Rough-in10/6/200410/6/200410/6/2004 12:00:00 AMPPART
Sprinkler supply is c900 blue brute with MJ 90 and ductile rise up to flange. 10/6/2004 12:06:19 PM
FIR04-00478 INSP-Final Inspection10/6/200410/6/200410/6/2004 12:00:00 AMPPASS
fire alarm finaled
FIR04-00256 INSP-Final Inspection10/5/200410/6/200410/6/2004 12:00:00 AMPNR
Existing smoke detectors do not release doors, infact they don't send any signals to the fire alarm panel 10/6/2004 2:03:44 PM
FIR04-00478 INSP-Final Inspection10/5/200410/6/200410/6/2004 12:00:00 AMPPASS
Fire life safety finaled 10/6/2004 2:00:58 PM
FIR04-00594 INSP-Final Inspection10/6/200410/6/200410/6/2004 12:00:00 AMPFAIL
Provide 14awg wire instead of 16awg as per plans. Provide verification on duct detector shutdown (plans). Plans show dual phone lines but there are no phone lines. There are sprinklers in the kitchen but actual head count is not known for possible sprinkler system monitoring 10/6/2004 3:17:38 PM
FIR04-00548 INSP-Sprinkler Rough-in/Hydro10/6/200410/6/200410/6/2004 12:00:00 AMPCANC
Contractor is not ready 10/6/2004 4:02:38 PM
FIR04-00573 INSP-Sprinkler Rough-in/Hydro10/6/200410/6/200410/6/2004 12:00:00 AMPPART
Hardlid areas as marked on plans are ok to cover 10/6/2004 3:26:50 PM