ELE05-02433
| Final | 10/6/2005 | 10/6/2005 | 10/6/2005 4:28:09 PM | P | PASS |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles correction made, ok to final
|
ELE05-03583
| Temporary Service | 10/6/2005 | 10/6/2005 | 10/6/2005 4:02:38 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr, left corr notice, 250.64(C) grounding electrode conductor shall be installed in one continuous length without a splice or joint.
|
ELE05-03671
| Temporary Service | 10/6/2005 | 10/6/2005 | 10/6/2005 3:10:21 PM | P | FAIL |
|
|
jim ###-#### called contr, left corr notice, fee due, 110.12(C) there shall be no broken parts, recpts, 312.5 conductors entering enclosure shall be protected from abrasion, 250.53(G) rod electrode shall be at least 8' long and driven to 8' depyh
|
ELE05-02935
| Final | 10/6/2005 | 10/6/2005 | 10/6/2005 2:57:55 PM | P | PASS |
|
|
entry code 3174; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok to final
|
ELE05-02898
| Final | 10/6/2005 | 10/6/2005 | 10/6/2005 2:12:34 PM | P | NR |
|
|
entry code 3174; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called contr, no access because floor stained. will recall
|
ELE05-03675
| Electrical Rough-In | 10/6/2005 | 10/6/2005 | 10/6/2005 12:35:40 PM | P | PART |
|
|
###-#### - dennis Note: early afternoon called elect, left corr notice for : BCC u/g needs inspection, 225.32 disconnect shall be installed, 225.36 disconnect shall be rated service rated, 110.3 wp equipment shall be installed, ric ceiling only ok
|
ELE05-03180
| Conference | 10/5/2005 | 10/6/2005 | 10/6/2005 10:42:43 AM | A | DONE |
|
|
Scheduled by a contractor via Hello! on 10/5/2005 at 1:08:59 PM. Contact: ###-####. talked about enclosures for steam press area
|
ELE05-00855
| Electrical Rough-In | 10/5/2005 | 10/6/2005 | 10/6/2005 10:02:46 AM | A | PASS |
|
|
CONTACT: LYLE DEAN - INSPECTION IS FOR THE 3RD FLOOR.; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok to cover 3rd floor parking deck anop
|
ELE05-03642
| Electrical Rough-In | 10/5/2005 | 10/6/2005 | 10/6/2005 9:30:04 AM | A | PASS |
|
|
jack Note: after 10:00 am; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok
|
ELE05-03556
| Final | 10/5/2005 | 10/6/2005 | 10/6/2005 9:02:07 AM | A | PASS |
|
|
READY FOR FINAL INSPECTION. WE HAVE INSTALLED THE REQUIRED GFI OUTLET. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr made, ok to final
|
ELE05-03035
| Final | 10/4/2005 | 10/6/2005 | 10/6/2005 8:38:10 AM | A | PASS |
|
|
barry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
ELE05-03599
| Rough-In Permanent Service | 10/6/2005 | 10/6/2005 | 10/6/2005 8:21:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 10/6/2005 at 6:13:44 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|