Inspections for the day of: Thursday, October 6, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02433 Final10/6/200510/6/200510/6/2005 4:28:09 PMPPASS
ron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles correction made, ok to final
ELE05-03583 Temporary Service10/6/200510/6/200510/6/2005 4:02:38 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr, left corr notice, 250.64(C) grounding electrode conductor shall be installed in one continuous length without a splice or joint.
ELE05-03671 Temporary Service10/6/200510/6/200510/6/2005 3:10:21 PMPFAIL
jim ###-#### called contr, left corr notice, fee due, 110.12(C) there shall be no broken parts, recpts, 312.5 conductors entering enclosure shall be protected from abrasion, 250.53(G) rod electrode shall be at least 8' long and driven to 8' depyh
ELE05-02935 Final10/6/200510/6/200510/6/2005 2:57:55 PMPPASS
entry code 3174; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok to final
ELE05-02898 Final10/6/200510/6/200510/6/2005 2:12:34 PMPNR
entry code 3174; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called contr, no access because floor stained. will recall
ELE05-03675 Electrical Rough-In10/6/200510/6/200510/6/2005 12:35:40 PMPPART
###-#### - dennis Note: early afternoon called elect, left corr notice for : BCC u/g needs inspection, 225.32 disconnect shall be installed, 225.36 disconnect shall be rated service rated, 110.3 wp equipment shall be installed, ric ceiling only ok
ELE05-03180 Conference10/5/200510/6/200510/6/2005 10:42:43 AMADONE
Scheduled by a contractor via Hello! on 10/5/2005 at 1:08:59 PM. Contact: ###-####. talked about enclosures for steam press area
ELE05-00855 Electrical Rough-In10/5/200510/6/200510/6/2005 10:02:46 AMAPASS
CONTACT: LYLE DEAN - INSPECTION IS FOR THE 3RD FLOOR.; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok to cover 3rd floor parking deck anop
ELE05-03642 Electrical Rough-In10/5/200510/6/200510/6/2005 9:30:04 AMAPASS
jack Note: after 10:00 am; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok
ELE05-03556 Final10/5/200510/6/200510/6/2005 9:02:07 AMAPASS
READY FOR FINAL INSPECTION. WE HAVE INSTALLED THE REQUIRED GFI OUTLET. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr made, ok to final
ELE05-03035 Final10/4/200510/6/200510/6/2005 8:38:10 AMAPASS
barry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
ELE05-03599 Rough-In Permanent Service10/6/200510/6/200510/6/2005 8:21:00 AMAPASS
Scheduled by a contractor via Hello! on 10/6/2005 at 6:13:44 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok