ELE06-02118
| Electrical Rough-In | 10/6/2006 | 10/6/2006 | 10/6/2006 2:58:25 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/6/2006 at 8:13:00 AM. Contact: ###-####. ok
|
ELE06-01637
| Final | 10/5/2006 | 10/6/2006 | 10/6/2006 2:36:30 PM | P | DONE |
|
|
Scheduled by a contractor via Hello! on 10/5/2006 at 8:32:24 PM. Contact: ###-####.
|
ELE06-03712
| Rough-In Permanent Service | 10/6/2006 | 10/6/2006 | 10/6/2006 2:01:08 PM | P | NR |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Patricia Smith needs addresses
|
ELE06-03707
| Electrical Rough-In | 10/5/2006 | 10/6/2006 | 10/6/2006 1:20:34 PM | P | NH |
|
|
Phone #: ###-#### Internet Inspection Request from: Patricia Smith notice posted called
|
ELE06-03206
| Final | 10/6/2006 | 10/6/2006 | 10/6/2006 1:04:38 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/6/2006 at 8:17:42 AM. Contact: ###-####. corr fee due, 314.20 needs box extensions all boxes, 250.122, needs #10 equip grd wire for 30 amp roof top units,406.4 recepts shall be secure, 250.104(A)(1) bond hot and cold, install track lights, power for gfci on roof, lockout clip for W H
|
ELE03-01602
| Final | 10/5/2006 | 10/6/2006 | 10/6/2006 10:23:40 AM | A | FAIL |
|
|
henry; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr. met owner 410.8 remove fixture and wiring bedrm closet no clearenec, 406.4 recepts not secure and shall be fluse with plates, 210.53 (A) install required outlet wall space fam rm
|
ELE06-03525
| Electrical Rough-In | 10/5/2006 | 10/6/2006 | 10/6/2006 9:48:23 AM | A | FAIL |
|
|
We wired a hot tub from the new 200 amp meter/panel.Please Final if OK. Tech/Jason/###-####. Thanks!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell corr. fee due, 680.26 FPN #8 bond shall terminate at spa equip, 352.10 shall use schedule *) pvc, 406.8 needs inuse cover called
|
ELE06-01958
| Final | 10/3/2006 | 10/6/2006 | 10/6/2006 9:23:19 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card not there
|
ELE06-00680
| ELE-Aging Inspection | 10/6/2006 | 10/6/2006 | 10/6/2006 7:57:19 AM | | PART |
|
|
wsuc
|
ELE06-00679
| ELE-Aging Inspection | 10/6/2006 | 10/6/2006 | 10/6/2006 7:56:57 AM | | PART |
|
|
wsuc
|