ELE06-03006
| Final | 10/6/2006 | 10/6/2006 | 10/6/2006 4:39:17 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok to final
|
ELE06-03007
| Final | 10/6/2006 | 10/6/2006 | 10/6/2006 3:40:20 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok to final
|
ELE05-02260
| Final | 10/5/2006 | 10/6/2006 | 10/6/2006 2:59:03 PM | A | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final, no card to sign
|
ELE06-03596
| Electrical Rough-In | 10/5/2006 | 10/6/2006 | 10/6/2006 2:49:47 PM | P | PASS |
|
|
Steve; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric ok
|
ELE06-03698
| Permanent Service | 10/6/2006 | 10/6/2006 | 10/6/2006 2:38:59 PM | P | FAIL |
|
|
brynt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left 2 messages, left corr notice, nec 550.11(A) a single disconnect shall be provided at an accessible location and plainly marked main,334.15(B) nm cable shall be protected from physical damage (below panel),310.15(B)(6) 200a breaker shall not protect 150a rated panel
|
ELE06-02921
| Permanent Service | 10/6/2006 | 10/6/2006 | 10/6/2006 1:49:31 PM | P | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s u/g n ok, 2 meters req'd, wrote corr notice nec 210.62 at least 1 recpt shall be installed for show windows 12' or fraction thereof
|
ELE06-03604
| Electrical Rough-In | 10/6/2006 | 10/6/2006 | 10/6/2006 1:13:59 PM | P | PASS |
|
|
UNDERGROUND INSPECTION FOR POLE LIGHT; Phone #: ###-#### Internet Inspection Request from: todd hall ok to cover u/g conduit only, gec not done yet
|
ELE06-03275
| Electrical Rough-In | 10/5/2006 | 10/6/2006 | 10/6/2006 10:34:21 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/5/2006 at 1:17:12 PM. Contact: ###-####. north 1/2 main floor ok to cover u/g, 3 sign boxes on mezz ok to cover
|
ELE06-03113
| Rough-In Permanent Service | 10/5/2006 | 10/6/2006 | 10/6/2006 10:03:09 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ric ok, p/s, u/g, n, ok
|
ELE06-01135
| Final | 10/5/2006 | 10/6/2006 | 10/6/2006 8:46:10 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas told owner to re-install cover plates on recpts, ok to final
|
ELE06-02311
| Electrical Rough-In | 10/5/2006 | 10/6/2006 | 10/6/2006 8:30:37 AM | A | PASS |
|
|
Reinspect underground, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters dug up u/g for inspection, ok to cover, green sticker on window
|