Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00319 ELE-Aging Inspection10/6/200810/6/200810/13/2008 9:19:35 AM DONE
see final, no esc this project
ELE08-02709 Conference10/6/200810/6/200810/6/2008 3:36:01 PMPDONE
pho Phone #: 1-###-#### met owner, looked at job, reviewed outlet spacing, 1 1/4", free conductor length, make-up, when to call for ri
ESC08-00729 General Inspection10/6/200810/6/200810/6/2008 3:23:01 PMPPASS
looked ok
ESC08-00483 Site Final10/6/200810/6/200810/6/2008 3:21:02 PMPPASS
looked ok, ok to final
ESC08-00084 General Inspection10/6/200810/6/200810/6/2008 3:18:38 PMPPASS
looked ok
ESC08-00365 General Inspection10/6/200810/6/200810/6/2008 3:17:27 PMAPASS
looked ok
ELE08-01563 Electrical Rough-In10/6/200810/6/200810/6/2008 3:16:23 PMPPASS
jason - underground Phone #: ###-#### ok to cover u/g east side and south part to re-feed sign
ELE08-02323 Final10/6/200810/6/200810/6/2008 2:39:53 PMPPASS
Good afternoon Bob,
The equipment is now labled and listed and ready for a final. Please call with 30min. notice so I can make sure the building is open and unlocked. Thx. Wayne Phone #: ###-#### Internet Inspection Request from: Wayne Craig corrections made, field evaluated by etl, ok to final, signed occupancy card
ELE08-02676 Permanent Service10/6/200810/6/200810/6/2008 1:41:34 PMPFAIL
met electrician, left correction notice, NEC 230.24(B) (4) service drop conductors shall be 18' over road, 344.30(A) shall rigidly support conduit within 3' of termination, 312.5 shall provide abrasion protection for all conductors entering enclosures,(meters), 110.26 shall provide work space about equipment, ref 550 mobile home parks, BCC shall inspect all u/g before cover, no violations shall be retained, no esc this project
ELE08-01956 Electrical Rough-In10/3/200810/6/200810/6/2008 10:16:47 AMAPASS
Phone #: ###-#### corrections made, soffits only ok to cover
ELE08-02694 Electrical Rough-In10/3/200810/6/200810/6/2008 9:27:32 AMAPASS
Re-inspect rough-in. Please call Jeff at ###-####.
Phone #: ###-#### Internet Inspection Request from: Spencer Mclean corrections made, ri ok, no esc this project
ELE08-02694 Permanent Service10/6/200810/6/200810/6/2008 9:27:08 AMAPASS
Re-inspect rough-in. Please call Jeff at ###-####.
Phone #: ###-#### Internet Inspection Request from: Spencer Mclean corrections made, p/s o/h rec ok, no esc this project
ELE08-02704 Rough-In Permanent Service10/3/200810/6/200810/6/2008 8:36:45 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Surerus called contractor, left corredction notice, NEC 300.4(A)&(D) edge of bored holes and mc cable shall be 1 1/4" from edge of framing members, 110.26(F)(1)(b) shall provide drip protection for foreign systems over and above dedicated space over panels, BCC shall provide permit for each meter and identify panel and main meter, approved set of plans shall be on job, no esc this project