Inspections for the day of: Monday, October 6, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-01042 INSP-Sprinkler Rough-in/Hydro10/6/200810/6/200810/6/2008 4:44:12 PMAFAIL
Inspection for the 1st floor failed due to field changes in pipe routing, head locations and floor plan layout in difference to the stamped approved plan set. Will need to provide accurate resubmittals for on site inspection prior to approval for ceiling cover.
FIR08-00516 INSP-Final Inspection10/3/200810/6/200810/6/2008 4:38:48 PMACANC
Bruce Phone #: ###-####
FIR08-00371 INSP-Final Inspection10/3/200810/6/200810/6/2008 4:37:59 PMPNH
Bill Phone #: ###-#### NOTE: Contractor not available on site
FIR07-00928 INSP-Sprinkler Rough-in/Hydro10/6/200810/6/200810/6/2008 4:36:22 PMAFAIL
Inspection for the attic antifreeze system only. Field installation does not match approved plans at several locations including the design area, added heads, pipe routing, deleted heads, etc. Will need to provide approved resubmittals reflecting field modifications prior to cover. Also noted one unprotected cavity, a missing hanger, bushings at all branchline upright heads-circled locations on plans.
BLD08-01547 FIRE-Final Inspection10/3/200810/6/200810/6/2008 2:55:38 PMAPASS
Fire life safety inspection passed. NOTE: Max occupant load signage at the two training/conference rooms to be posted as discussed-will verify at next site visit.
BLD08-01224 FIRE-Final Inspection10/3/200810/6/200810/6/2008 2:53:21 PMAPASS
Fire life safety passed.
FIR08-00610 INSP-Final Inspection10/6/200810/6/200810/6/2008 2:52:12 PMPPASS
Noted deficiencies corrected, storage room spacing adjusted, fire sprinkler permit finaled.
FIR08-00597 INSP-Final Inspection10/6/200810/6/200810/6/2008 2:50:54 PMPPASS
Fire sprinkler permit final inspection passed.
BLD07-03163 FIRE-Final Inspection10/6/200810/6/200810/6/2008 2:47:39 PMAPART
Items needed prior to permit fire life safety final include repair one EM exit discharge light at the main entry, spin the SW hydrant 180 deg. to face the building, provide one fire extinguisher at the cylinder pick/sort area #132 when racking is installed, the spray booth fire sprinkler permit work needs to be completed inspected and approved, noted work at the fuel island is not finished at this time. Recieved signed letter from Musgrove Engineering regarding gas control system functionality per design requirements. Okay to begin equipment installation per agreements on file.
BLD07-03163 FIRE-Alarm Testing10/6/200810/6/200810/6/2008 2:33:15 PMADONE
Duplicate inspection request.
FIR08-00289 INSP-Final Inspection10/3/200810/6/200810/6/2008 2:32:03 PMAPASS
Three C/N items repaired, forward flow testing completed acceptable, fire sprinkler permit finaled.
FIR08-00278 INSP-Final Inspection10/3/200810/6/200810/6/2008 2:30:12 PMAPART
Correction items per last inspection verified for completion, alarm testing passed, permit finaled.
FIR08-00424 INSP-Final Inspection10/3/200810/6/200810/6/2008 10:30:36 AMANR
Equipment is not yet installed, permit work not completed for inspection at this time.