BLD11-02405
| FIRE-Final Inspection | 10/5/2011 | 10/6/2011 | 10/7/2011 4:47:26 PM | P | CANC |
|
|
Overbooked
|
FIR11-00194
| INSP-Sprinkler Rough-in | 10/6/2011 | 10/6/2011 | 10/7/2011 9:47:46 AM | P | CANC |
|
|
Overbooked
|
FIR11-00542
| INSP-Sprinkler Rough-in | 10/6/2011 | 10/6/2011 | 10/7/2011 9:47:16 AM | P | CANC |
|
|
Overbooked
|
FIR11-00343
| INSP-Final Inspection | 10/5/2011 | 10/6/2011 | 10/6/2011 4:59:51 PM | P | FAIL |
|
|
Two non-functional MP stations at the 2nd floor need repaired, flow switch at the main riser is not operable. Notification testing, sprinkler riser supervision, new and relocated SD's tested okay.
|
FIR11-00355
| INSP-Final Inspection | 10/6/2011 | 10/6/2011 | 10/6/2011 4:53:09 PM | P | PART |
|
|
Final walkthrough completed, minor adjustments done while on site. Verified added head at the dry valve room. Fire alarm interconnections tested. Final pending repair of non-functional waterflow switch at the main riser.
|
FIR11-00072
| INSP-Final Inspection | 10/6/2011 | 10/6/2011 | 10/6/2011 4:48:36 PM | P | CANC |
|
|
Overbooked
|
BLD11-00416
| FIRE-Final Inspection | 10/5/2011 | 10/6/2011 | 10/6/2011 4:44:19 PM | P | NR |
|
|
john Phone #: ###-####
|
FIR11-00414
| INSP-Sprinkler Rough-in | 10/5/2011 | 10/6/2011 | 10/6/2011 4:36:07 PM | P | CANC |
|
|
overbooked
|
FIR11-00506
| INSP-Final Inspection | 10/6/2011 | 10/6/2011 | 10/6/2011 2:28:25 PM | P | PASS |
|
|
Correction items completed, functional testing passed. Fire alarm permit finaled.
|
FIR11-00355
| INSP-Sprinkler Rough-in/Hydro | 10/5/2011 | 10/6/2011 | 10/6/2011 12:45:52 PM | A | PASS |
|
|
OH hydrostatic re-test passed.
|
FIR11-00506
| INSP-Final Inspection | 10/5/2011 | 10/6/2011 | 10/6/2011 12:29:25 PM | A | FAIL |
|
|
Detectors for door release service shall be installed per NFPA 72 2010 17.7.5.6.6.1.
|
BLD11-00125
| FIRE-Final Inspection | 10/6/2011 | 10/6/2011 | 10/6/2011 12:21:06 PM | A | FAIL |
|
|
Noted missing exit signs and EM lighting per plan at the 2nd, 1st and basement levels- see A and E sheets on stamped plan set for locations, remove cover at the FACP smoke detector, repair one non-functional light at an EM adjacent to the restrooms, remove non-required signage at 2nd floor door 29, door 8e appears to need hardware group 4, provide approved hardware at the bar door to basement stairs.
|
BLD11-00125
| FIRE-Final Inspection | 10/6/2011 | 10/6/2011 | 10/6/2011 12:13:38 PM | A | FAIL |
|
|
See plan annotations.
|
BLD11-00125
| FIRE-Final Inspection | 10/5/2011 | 10/6/2011 | 10/5/2011 4:34:06 PM | A | CANC |
|
|
I am ready for the fire/life safety inspection. Phone #: ###-#### >> Inspection requested via web by Scott Asin Inspection cancelled from web by: Scott Asin
|