Inspections for the day of: Thursday, October 6, 2011.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02405 FIRE-Final Inspection10/5/201110/6/201110/7/2011 4:47:26 PMPCANC
Overbooked
FIR11-00194 INSP-Sprinkler Rough-in10/6/201110/6/201110/7/2011 9:47:46 AMPCANC
Overbooked
FIR11-00542 INSP-Sprinkler Rough-in10/6/201110/6/201110/7/2011 9:47:16 AMPCANC
Overbooked
FIR11-00343 INSP-Final Inspection10/5/201110/6/201110/6/2011 4:59:51 PMPFAIL
Two non-functional MP stations at the 2nd floor need repaired, flow switch at the main riser is not operable. Notification testing, sprinkler riser supervision, new and relocated SD's tested okay.
FIR11-00355 INSP-Final Inspection10/6/201110/6/201110/6/2011 4:53:09 PMPPART
Final walkthrough completed, minor adjustments done while on site. Verified added head at the dry valve room. Fire alarm interconnections tested. Final pending repair of non-functional waterflow switch at the main riser.
FIR11-00072 INSP-Final Inspection10/6/201110/6/201110/6/2011 4:48:36 PMPCANC
Overbooked
BLD11-00416 FIRE-Final Inspection10/5/201110/6/201110/6/2011 4:44:19 PMPNR
john Phone #: ###-####
FIR11-00414 INSP-Sprinkler Rough-in10/5/201110/6/201110/6/2011 4:36:07 PMPCANC
overbooked
FIR11-00506 INSP-Final Inspection10/6/201110/6/201110/6/2011 2:28:25 PMPPASS
Correction items completed, functional testing passed. Fire alarm permit finaled.
FIR11-00355 INSP-Sprinkler Rough-in/Hydro10/5/201110/6/201110/6/2011 12:45:52 PMAPASS
OH hydrostatic re-test passed.
FIR11-00506 INSP-Final Inspection10/5/201110/6/201110/6/2011 12:29:25 PMAFAIL
Detectors for door release service shall be installed per NFPA 72 2010 17.7.5.6.6.1.
BLD11-00125 FIRE-Final Inspection10/6/201110/6/201110/6/2011 12:21:06 PMAFAIL
Noted missing exit signs and EM lighting per plan at the 2nd, 1st and basement levels- see A and E sheets on stamped plan set for locations, remove cover at the FACP smoke detector, repair one non-functional light at an EM adjacent to the restrooms, remove non-required signage at 2nd floor door 29, door 8e appears to need hardware group 4, provide approved hardware at the bar door to basement stairs.
BLD11-00125 FIRE-Final Inspection10/6/201110/6/201110/6/2011 12:13:38 PMAFAIL
See plan annotations.
BLD11-00125 FIRE-Final Inspection10/5/201110/6/201110/5/2011 4:34:06 PMACANC
I am ready for the fire/life safety inspection. Phone #: ###-#### >> Inspection requested via web by Scott Asin Inspection cancelled from web by: Scott Asin