Inspections for the day of: Monday, October 6, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01179 ELE-Aging Inspection10/6/201410/6/201410/6/2014 3:03:56 PM DONE
Waiting on owner
ELE14-02768 Electrical Rough-In10/6/201410/6/201410/6/2014 2:59:23 PMPPASS
Please call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson Floor heat rough in ok cover
ELE14-02280 Final10/5/201410/6/201410/6/2014 2:07:17 PMPPASS
final inspection building A contact ####-#### andy . Phone #: ###-#### Inspection requested via web by andrew dopieralski Final ok
ELE14-02753 Rough-In Permanent Service10/2/201410/6/201410/6/2014 1:18:45 PMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
ELE14-02730 Final10/3/201410/6/201410/6/2014 12:11:41 PMACANC
Phone #: ###-#### Inspection requested via web by Greg Traudt Needed ri p/s
ELE14-02730 Rough-In Permanent Service10/1/201410/6/201410/6/2014 12:10:36 PMAPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt Rough in ok cover p/s u/g n ok
ELE14-02710 Conference10/6/201410/6/201410/6/2014 11:27:45 AMPDONE
Conference to figure out ufer ground Phone #: ###-#### Inspection requested via web by Thomas Jenkins Concrete encased and building steel are grounding electrodes for this service. 250.52 Grounding Electrodes.
(A) Electrodes Permitted for Grounding
(3) Concrete-Encased Electrode. A concrete-encased electrode
shall consist of at least 6.0 m (20 ft) of either (1) or (2):
(1) One or more bare or zinc galvanized or other electrically
conductive coated steel reinforcing bars or rods of
not less than 13 mm (1/2 in.) in diameter, installed in
one continuous 6.0 m (20 ft) length, or if in multiple
pieces connected together by the usual steel tie wires,
exothermic welding, welding, or other effective means
to create a 6.0 m (20 ft) or greater length; or
(2) Bare copper conductor not smaller than 4 AWG
ELE14-02334 Final10/5/201410/6/201410/6/2014 11:13:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Chris Berthelot Final ok
ELE14-02335 Final10/5/201410/6/201410/6/2014 11:12:54 AMAPART
Phone #: ###-#### Inspection requested via web by Chris Berthelot Bldg ok occupy parking lot pole lights not ready.
ELE14-01666 Final10/6/201410/6/201410/6/2014 10:47:16 AMAPART
Please call me. We need to get a partial final. They want a partial occupancy.
Thank you, Greg. Phone #: ###-#### Inspection requested via web by Greg Idsinga Spaces 7, 12 thru 28 ok occupy.
Unfinished spaces 1 thru 6 and 8 thru 11 not ready
ELE14-00775 Electrical Rough-In10/6/201410/6/201410/6/2014 10:03:33 AMAPASS
Ceiling Cover. Toby is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen maternity and nurses area grid rough in ok cover
ELE14-02758 Permanent Service10/3/201410/6/201410/6/2014 9:42:23 AMAFAIL
Re energize, power off over a year. Phone #: ###-#### Inspection requested via web by Eric Schroeder BCC- To energize service which has been off for extended period of time grounding shall be brought up to current code cycle, 2008.
250.53(A)(2)- Single piping system shall be supplemented by additional grounding electrode.
4-05-32- Code violation not to be retained.
334.40- NM cable splice or tap shall be in a box. NM cable shall not be installed where subject to physical damage.