ELE13-01726
| ELE-Aging Inspection | 10/6/2015 | 10/6/2015 | 10/7/2015 3:41:27 PM | | DONE |
|
|
Called contracor. Job completed by others ele 13-02806
|
ELE15-03201
| Final | 10/6/2015 | 10/6/2015 | 10/6/2015 4:11:14 PM | P | FAIL |
|
|
Please call ahead of time, Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker 350.12(1)- LFMC shall not be installed wher subject to physical damage. 300.5(D)(4)- Shere conductors emerge from grade they are concidered subject to physical damage and shall be protected by heavy wall conduit, rigid, IMC, or SCH 80 PVC. 590.6(B)- Use of other outlets. Temp power used for construction shall have GFCI protection.
|
ELE15-03187
| Electrical Rough-In | 10/5/2015 | 10/6/2015 | 10/6/2015 3:20:15 PM | P | PART |
|
|
have couple lights an outlets to do atthis time but will more likely be ready by 10 am so any time after or if in neighbor hood sooner stop by Phone #: ###-#### Inspection requested via web by dennis mcneely 210.11(C)(3)- Bathroom receptacle outlets shall be on a dedicated ciruit and shall have not other outlets. 240.4(D)(3)- 15 amp max over courrent protection on 14 ga. wire. OK cover all except receptacle wall.
|
ELE15-03186
| Final | 10/6/2015 | 10/6/2015 | 10/6/2015 2:49:55 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Randy Fletcher All wiring fished in for bath remodel. Final ok
|
ELE15-03098
| Final | 10/6/2015 | 10/6/2015 | 10/6/2015 2:27:42 PM | P | PASS |
|
|
John Phone #: ###-#### Final ok
|
ELE15-03211
| Electrical Rough-In | 10/6/2015 | 10/6/2015 | 10/6/2015 1:58:32 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Eddy Udry Existing knob and tube to remain in free air. kitchen and laundry room rough in ok cover
|
ELE15-03199
| Final | 10/5/2015 | 10/6/2015 | 10/6/2015 1:37:10 PM | A | PASS |
|
|
Dave-hooking service back up Phone #: ###-#### Homeowner is foreman for RME, no conference needed. Final ok
|
ELE15-03199
| Permanent Service | 10/6/2015 | 10/6/2015 | 10/6/2015 1:36:14 PM | P | PASS |
|
|
Dave-hooking service back up Phone #: ###-#### Changing from overhead service to underground. p/s u/g rec ok
|
ELE15-01821
| Final | 10/5/2015 | 10/6/2015 | 10/6/2015 12:53:47 PM | A | FAIL |
|
|
Inspection requested via web by Steve Craig 400.8- Wiring for split system. Flexible cords shall not be ran through walls or installed in a wall. 406.12- All 15 and 20 amp 120 volt receptacle outlets installed in a dwelling shall be tamper resistant type. Kit GFI and washer. 422.30- A disconnecting means shall be provided with in sight of water heater. 110.25- lock out acceptable. No contact information provided
|
ELE15-03033
| Final | 10/5/2015 | 10/6/2015 | 10/6/2015 12:08:46 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON Final ok
|
ELE15-01111
| Electrical Rough-In | 10/5/2015 | 10/6/2015 | 10/6/2015 11:52:18 AM | A | PASS |
|
|
We need a grid inspection for tomorrow. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Grid tiles near couple open boxes to remain open. Auto repair bay area grid rough in ok cover
|
ELE15-02968
| Final | 10/5/2015 | 10/6/2015 | 10/6/2015 11:29:26 AM | A | PASS |
|
|
We are requesting a final inspection for this project tomorrow 10/6/15 our contact is Todd @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate Final ok
|
ELE15-03088
| Permanent Service | 10/6/2015 | 10/6/2015 | 10/6/2015 11:12:00 AM | P | PASS |
|
|
p/s u/g n ok
|
ELE15-03180
| Final | 10/2/2015 | 10/6/2015 | 10/6/2015 11:06:48 AM | A | FAIL |
|
|
Air Cond Circuit from panel to A/C Phone #: ###-#### Inspection requested via web by Rick Beckman 440.4- Over current shall be sized to nameplate rating. 15 amp max, 25 amp installed.
|
ELE15-03208
| Electrical Rough-In | 10/6/2015 | 10/6/2015 | 10/6/2015 10:47:19 AM | A | PASS |
|
|
rough in led pole heads Phone #: ###-#### Inspection requested via web by Tim Dunlop Listing confirmed. Rough in ok
|
ELE15-02983
| Final | 10/5/2015 | 10/6/2015 | 10/6/2015 10:36:04 AM | A | FAIL |
|
|
Code to door if needed is 9500 Phone #: ###-#### Inspection requested via web by Brad Baker 210.8(B)(5)- All 15 and 20 amp 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. 110.3(B)- Confirm listing of x-ray unit and controller as listed system. 300.4(G)- Conduits with #4 or larger conductor shall have a bushing to protect conductors. 330.30(B)- MC cable shall be secured within 12" of panel. * Several receptacle outlets in offices not working.
|
ELE15-03182
| Rough-In Permanent Service | 10/6/2015 | 10/6/2015 | 10/6/2015 9:32:37 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 334.30- NM cable shall be secured with in 12" of a box and with in 4 1/2' of upper plate. 201 bed and 102 bath. * mudring missing of up bath 202
|
ELE15-03210
| Temporary Service | 10/6/2015 | 10/6/2015 | 10/6/2015 8:43:10 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE15-03161
| Temporary Service | 10/5/2015 | 10/6/2015 | 10/6/2015 8:28:36 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
|