Inspections for the day of: Thursday, October 6, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-02590 Electrical Rough-In10/5/201610/6/201610/6/2016 1:57:43 PMPPASS
In wall inspection for the afternoon of 10/6/16

If you have questions please contact Dylan Pierce at ###-####

Thanks Phone #: ###-#### Inspection requested via web by Darren Larsen
NE and NW exterior walls as noted on GC print only ok cover
ELE16-02844 Final10/6/201610/6/201610/6/2016 1:18:43 PMPFAIL
Call for access Phone #: ###-#### Inspection requested via web by John VanZandt
314.25 cover required for open box in ceiling near panel
receptacles shall not be locate above ceiling grids
ELE16-00580 Permanent Service10/5/201610/6/201610/6/2016 12:41:59 PMAFAIL
The Fowler
Contact Lonny Baum
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Avaliable fault current needed
Main bonding jumper shall be upsized as per 250.66
ELE16-02378 Final10/5/201610/6/201610/6/2016 9:53:29 AMAFAIL
Justin Phone #: ###-####
BCO all units need indentification
All units need access
Base board heaters loose
110.7 shall be free from shorts-whole 8 plex needs to be gone through
ELE16-02377 Final10/5/201610/6/201610/6/2016 9:51:57 AMAFAIL
Justin Phone #: ###-####
All units need access unit#1
BCO all units need identification
ELE16-02376 Final10/5/201610/6/201610/6/2016 9:49:18 AMAFAIL
Justin Phone #: ###-####
110.21 reverse polarity in upper south unit in living room
BCO units shall be identified
room #4 no access
408.4 panel schedules needed
ELE16-03086 Final10/5/201610/6/201610/6/2016 8:39:21 AMAPASS
The Corrections Are,Done The Only BoxI Could Find In The Basement Was,Where The Furnace Switch I Missed Was,Supposed To Go..Should Be All Giid Phone #: ###-#### Inspection requested via web by jason shifflett
Corrections fixed final ok
ELE16-03253 Electrical Rough-In10/5/201610/6/201610/6/2016 8:19:41 AMAPASS
Call for access, number on apt. Is 3953 but address is 3905. Call with questions, thank you Phone #: ###-#### Inspection requested via web by John VanZandt
Adress is strange due to tax reason address comes wrong. Laundry off kitchen ok cover