Inspections for the day of: Friday, October 6, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00231 INSP-Final Inspection10/6/201710/6/201710/6/2017 3:48:56 PMPPASS
Final inspection for wet standpipes passed/complete
FIR16-00090 INSP-Final Inspection10/6/201710/6/201710/6/2017 3:47:17 PMPPASS
Final inspection for this permit passed/complete.
BLD15-03489 FIRE-Final Inspection10/6/201710/6/201710/6/2017 3:45:13 PMPPART
Defeciency list items for TCO requested levels, level 1 and levels 4 through 9 have been repaired with exception to the areas missing the photo luminescent tape on the handrails, Life fire safety inspection complete for TCO covered areas, TCO authorized for life fire safety per conversation with Ron Johnson.
FIR17-00579 INSP-Sprinkler Rough-in10/6/201710/6/201710/6/2017 2:40:42 PMPPART
Partial rough to cover for underground supply complete, stub up to approximately 15 feet from stub up approved for cover. Remaining underground to be installed at a later date.
FIR16-00675 INSP-Sprinkler Rough-in10/5/201710/6/201710/6/2017 11:22:25 AMPPASS
Rough to ocver inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
BLD17-00961 FIRE-Final Inspection10/6/201710/6/201710/6/2017 10:43:40 AMPPASS
No fire sprinkler modifications, fire alarm inspection is complete, fire extinguishers are in common area's with current inspection tags. Final life fire safety inspection for area of work passed/complete.
BLD17-01519 FIRE-Final Inspection10/5/201710/6/201710/6/2017 10:40:42 AMAPASS
Repair has been made to emergency lighting, final life fire safety inspection passed/complete.
FIR17-00509 INSP-Final Inspection10/6/201710/6/201710/6/2017 10:11:32 AMAPASS
Final fire alarm inspection passed/complete.
FIR17-00308 INSP-Final Inspection10/4/201710/6/201710/6/2017 10:11:04 AMAFAIL
Isolation valve for fire sprinkler system is required per fire sprinkler permit review.
FIR17-00509 INSP-Alarm Testing10/4/201710/6/201710/6/2017 9:00:13 AMADONE
Alarm testing complete