Inspections for the day of: Tuesday, October 7, 2003.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00363 FIR-Aging Inspection10/7/200310/7/200310/7/2003 12:00:00 AM PASS
wip 10/7/2003 1:01:25 PM
BLD03-01954 FIRE-Sprinkler Rough-in10/3/200310/7/200310/7/2003 12:00:00 AMAPART
Don Bryan, ###-#### okay to cover; will need to verify proper heads in spare head box and annual inspection is current for sprinkler system 10/7/2003 10:56:31 AM
FIR03-00571 INSP-Sprinkler Rough-in10/6/200310/7/200310/7/2003 12:00:00 AMAPART
Please call 1 hour prior to arrival;; Phone #: ###-#### Internet Inspection Request from: Trent Bice UG cover inspection only - okay; still need hydro and flush; 10/7/2003 12:59:22 PM
BLD02-01217 FIRE-Final Inspection10/6/200310/7/200310/7/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 10/6/2003 at 11:38:10 AM. Contact: ###-####.
FIR03-00595 INSP-Sprinkler Rough-in/Hydro10/6/200310/7/200310/7/2003 12:00:00 AMAPART
sam ; Phone #: ###-#### Internet Inspection Request from: Annette Moore UG cover okay; still need hydro and flush 10/7/2003 12:58:30 PM
FIR03-00357 INSP-Final Inspection10/6/200310/7/200310/7/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 10/6/2003 at 9:19:20 PM. Contact: ###-####.
FIR03-00375 INSP-Sprinkler Rough-in/Hydro10/6/200310/7/200310/7/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/6/2003 at 1:41:13 PM. Contact: ###-####. okay to cover 2nd floor only except room 209 as it has protective cover on head; the branch line on the north side of the new addition is not installed; the new wet part of the riser is not complete; canopies not installed on all 401 heads; will need spare heads in head box; branch line on east side not complete; this building will now have over 20 heads and will require monitoring and does not have complete sprinkler coverage 10/7/2003 3:24:35 PM
FIR03-00536 INSP-Sprinkler Rough-in10/7/200310/7/200310/7/2003 12:00:00 AMPPART
okay to cover 10/7/2003 10:55:57 AM
FIR03-00268 INSP-Final Inspection10/7/200310/7/200310/7/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 10/7/2003 at 11:25:04 AM. Contact: ###-####. need to reschedule when other fire/life safety items are ready 10/8/2003 7:39:29 AM
BLD03-00482 FIRE-Final Inspection10/7/200310/7/200310/7/2003 12:00:00 AMPPASS