Inspections for the day of: Thursday, October 7, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-02861 Final10/6/200410/7/200410/7/2004 12:00:00 AMAPASS
CONTACT: SHANE KORTE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy called Shane will remove outlet too close to tub and blank it off 10/7/2004 9:13:45 AM
ELE04-02172 Final10/6/200410/7/200410/7/2004 12:00:00 AMAFAIL
brandon Note: please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles needs permit for pump wiring done by general contractor? called electrical contractor.
hold put on job 10/7/2004 8:52:02 AM
ELE04-01589 Rough-In Permanent Service10/6/200410/7/200410/7/2004 12:00:00 AMAFAIL
###-#### brian called needs guy kit, and bonding type meyers hub 10/7/2004 10:30:57 AM
ELE04-03051 Electrical Rough-In10/6/200410/7/200410/7/2004 12:00:00 AMAPASS
grounding insp todd ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 10/7/2004 8:10:22 AM
ELE04-03081 Electrical Rough-In10/6/200410/7/200410/7/2004 12:00:00 AMPPART
###-#### john u/g and bond ok contractor will call for bonding of pool cover metal when ready 10/7/2004 3:27:33 PM
ELE04-03085 Final10/7/200410/7/200410/7/2004 12:00:00 AMPFAIL
###-#### - henry cor. posted called u/g covered before inspection, strap all pvc, provide switch, light, gfci recept in crawl for pump equipment, flex not approved for u/g in crawl space protecting uf cable 10/7/2004 12:55:05 PM
ELE04-03078 Rough-In Permanent Service10/7/200410/7/200410/7/2004 12:00:00 AMPFAIL
alan ###-#### re-insp changed address from 616 w jefferson to 618 e jefferson per mapping
cor. posted called nail plates and 1 1/4", 312.5 connectors for cables back of panel, grd to concrete encased electrode,, uncover u/g to garage covered before inspection, 210.52(E) &210.63 outlet for outside back and within 25 ft of a/c 10/7/2004 4:08:58 PM
ELE04-01922 Rough-In Permanent Service10/7/200410/7/200410/7/2004 12:00:00 AMPPASS
CONTACT: SHANE KORTE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy p/s o/h rec. ok 10/7/2004 12:55:27 PM
ELE04-03095 Electrical Rough-In10/7/200410/7/200410/7/2004 12:00:00 AMPNR
brad ###-#### called need to meet contractor and need plans at site with rooms marked 10/7/2004 3:01:24 PM
ELE04-01922 Final10/7/200410/7/200410/7/2004 12:00:00 AMPPASS
ok