Inspections for the day of: Thursday, October 7, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS03-00229 MIS-Aging Inspection10/7/200410/7/200410/13/2004 12:00:00 AM PASS
The item holding signing this off is the extinguishing system hood as the lights don't shut off upon activation; talked to Mike of General Fire and he has talked to the electrical contractor and the lights will be disconnected and then he will call for a final on the hood permit 10/13/2004 8:29:19 AM
BLD02-03091 BLD-Aging Inspection10/7/200410/7/200410/7/2004 12:00:00 AM PASS
PDS fire code office is working with Garden City water department to get a flow test of the area to determine water available as it is in question due to the fire pump not being able to pump 750 gpm; this may require an additional pump flow test 10/7/2004 9:26:29 AM
FIR04-00372 INSP-Final Inspection10/7/200410/7/200410/7/2004 12:00:00 AMAPASS
BLD04-00539 FIRE-Final Inspection10/7/200410/7/200410/7/2004 12:00:00 AMPPASS
ivan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
FIR02-00411 INSP-Final Inspection10/5/200410/7/200410/7/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/5/2004 at 3:19:20 PM. Contact: ###-####. Completed all phases of this permit; need to verify with Mary if any other submittals are needed to plan review 10/8/2004 7:58:32 AM
FIR04-00245 INSP-Final Inspection10/7/200410/7/200410/7/2004 12:00:00 AMPPART
Tested the area of east annex - okay; will need to test area west of 2 hour wall 10/8/2004 7:59:46 AM
FIR04-00352 INSP-Final Inspection10/7/200410/7/200410/7/2004 12:00:00 AMPPASS
FIR04-00606 INSP-Sprinkler Rough-in/Hydro10/7/200410/7/200410/7/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/7/2004 at 9:03:32 AM. Contact: ###-####.