Inspections for the day of: Friday, October 7, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02465 Electrical Rough-In10/7/200510/7/200510/7/2005 4:16:47 PMPPASS
Scheduled by a contractor via Hello! on 10/7/2005 at 7:44:25 AM. Contact: ###-####. all u/g for parking lot ok
ELE05-02656 Final10/6/200510/7/200510/7/2005 3:38:56 PMPPASS
Scheduled by a contractor via Hello! on 10/6/2005 at 2:06:18 PM. Contact: ###-####. ok card signed
ELE05-01703 Final10/7/200510/7/200510/7/2005 3:38:32 PMPPASS
ELE05-00351 Final10/7/200510/7/200510/7/2005 2:38:36 PMAPASS
###-#### emmett final ok survey posted for light fixtures 4 wall sconce, shall provide a non combustile back for wooden canopy,410.39 electrical contractor will accept responsibilty for fixtures
ELE05-03489 Permanent Service10/7/200510/7/200510/7/2005 2:35:50 PMPPASS
jim ###-#### p/s u/g new for meter T-Mobile
ELE05-03215 Rough-In Permanent Service10/7/200510/7/200510/7/2005 1:33:21 PMPPART
Inspection Underground Partial Completion ; Phone #: ###-#### Internet Inspection Request from: Cathy Felin ok
ELE05-03683 Temporary Service10/7/200510/7/200510/7/2005 12:40:17 PMPPASS
rick ###-#### t/s u/g new ok
ELE05-03539 Temporary Service10/7/200510/7/200510/7/2005 12:39:53 PMPFAIL
Scheduled by a contractor via Hello! on 10/7/2005 at 9:50:24 AM. Contact: ###-####. cor. called 250.53(G) grd rod shall be flush with grade, 110.12(C) clean dirt from t/s
ELE05-03664 Rough-In Permanent Service10/6/200510/7/200510/7/2005 11:36:46 AMAPASS
Charlie Internet Inspection Request from: Melyne Davis r/i ok p/s u/g new ok
ELE05-02374 Electrical Rough-In10/6/200510/7/200510/7/2005 10:39:42 AMAPART
underground inspection; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen u/g conduit and boxes ok
ELE05-03510 Electrical Rough-In10/7/200510/7/200510/7/2005 10:21:46 AMPPASS
please call 30 mins prior to inspection///steve; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. made r/i ok
ELE05-03670 Temporary Service10/6/200510/7/200510/7/2005 8:49:36 AMAFAIL
corner of N. Redway Rd. and W. Pomona Rd.
contact Neal Rumsey ###-####; Phone #: ###-#### Internet Inspection Request from: Julie Schroder cor. called 110.12(C) clean dirt from t/s
ELE05-03232 Final10/6/200510/7/200510/7/2005 8:13:17 AMANH
need a final inspection the door is open. If there is any problem please call jean ###-####; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
notice posted called
ELE05-03489 Final10/7/200510/7/200510/7/2005 12:00:00 AMPPASS
jim ###-#### ok