ELE05-02806
| Electrical Rough-In | 10/7/2005 | 10/7/2005 | 10/7/2005 4:10:40 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen met with contractor, left correction notice, BCC no violations shall be retained, 358.30 Emt shall be fastened within 3' of box, 330.30(B) mc cable shall be strapped within 12" of box, 250.64(B) gec shall be secured in place,BCC no cover shall be done prior to inspection, 250.86 metal boxes shall be grounded
|
ELE05-03686
| Electrical Rough-In | 10/7/2005 | 10/7/2005 | 10/7/2005 3:58:13 PM | P | FAIL |
|
|
dan ###-#### called contr, left corr notice,300.4(D) mc cable shall be 1 1/4" from edge of framing member,358.30(A) emt shall be strapped within 3' of box, 312.5 conductors entering enclosures shall be protected from abrasion, 348.30 flex shall be supported within 12" of box, 210.8(B) bath recpt shall be gfci , 300.11(A) raceways shall not be supported by ceiling grids, BCC no violations shall be retained
|
ELE05-03662
| Rough-In Permanent Service | 10/7/2005 | 10/7/2005 | 10/7/2005 3:13:03 PM | P | PASS |
|
|
clyde; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok, p/s u/g n ok
|
ELE05-03014
| Electrical Rough-In | 10/7/2005 | 10/7/2005 | 10/7/2005 3:06:19 PM | P | PART |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover party room A & B ceilings only
|
ELE05-03687
| Rough-In Permanent Service | 10/7/2005 | 10/7/2005 | 10/7/2005 2:32:38 PM | P | PASS |
|
|
after 2 please////ron ###-#### ric ok, p/s u/g n ok
|
ELE05-03624
| Electrical Rough-In | 10/7/2005 | 10/7/2005 | 10/7/2005 1:14:53 PM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen front walls and area over panels not to be covered. rest of walls and baths ok to cover
|
ELE05-00855
| Electrical Rough-In | 10/6/2005 | 10/7/2005 | 10/7/2005 10:16:29 AM | A | PART |
|
|
CONTACT: LYLE DEAN - 3RD FLOOR PARKING GARAGE RAMP INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ramp 3rd fl ok to pour anop
|
ELE05-02260
| Electrical Rough-In | 10/6/2005 | 10/7/2005 | 10/7/2005 9:14:37 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/6/2005 at 3:02:09 PM. upper level wall ok to cover anop
|
ELE05-03611
| Permanent Service | 10/6/2005 | 10/7/2005 | 10/7/2005 9:12:45 AM | A | PASS |
|
|
lana; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr made, p/s o/h re-connect ok
|
ELE05-03591
| Electrical Rough-In | 10/6/2005 | 10/7/2005 | 10/7/2005 8:42:31 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/6/2005 at 3:58:23 PM. Contact: ###-####. wall cover only break room, office area anop. need to see bath switches, ok to 1 side bath walls only.
|
ELE05-03583
| Temporary Service | 10/7/2005 | 10/7/2005 | 10/7/2005 8:37:36 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corrections made, t/s u/g n ok
|