Inspections for the day of: Friday, October 7, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02806 Electrical Rough-In10/7/200510/7/200510/7/2005 4:10:40 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen met with contractor, left correction notice, BCC no violations shall be retained, 358.30 Emt shall be fastened within 3' of box, 330.30(B) mc cable shall be strapped within 12" of box, 250.64(B) gec shall be secured in place,BCC no cover shall be done prior to inspection, 250.86 metal boxes shall be grounded
ELE05-03686 Electrical Rough-In10/7/200510/7/200510/7/2005 3:58:13 PMPFAIL
dan ###-#### called contr, left corr notice,300.4(D) mc cable shall be 1 1/4" from edge of framing member,358.30(A) emt shall be strapped within 3' of box, 312.5 conductors entering enclosures shall be protected from abrasion, 348.30 flex shall be supported within 12" of box, 210.8(B) bath recpt shall be gfci , 300.11(A) raceways shall not be supported by ceiling grids, BCC no violations shall be retained
ELE05-03662 Rough-In Permanent Service10/7/200510/7/200510/7/2005 3:13:03 PMPPASS
clyde; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok, p/s u/g n ok
ELE05-03014 Electrical Rough-In10/7/200510/7/200510/7/2005 3:06:19 PMPPART
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover party room A & B ceilings only
ELE05-03687 Rough-In Permanent Service10/7/200510/7/200510/7/2005 2:32:38 PMPPASS
after 2 please////ron ###-#### ric ok, p/s u/g n ok
ELE05-03624 Electrical Rough-In10/7/200510/7/200510/7/2005 1:14:53 PMPPART
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen front walls and area over panels not to be covered. rest of walls and baths ok to cover
ELE05-00855 Electrical Rough-In10/6/200510/7/200510/7/2005 10:16:29 AMAPART
CONTACT: LYLE DEAN - 3RD FLOOR PARKING GARAGE RAMP INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ramp 3rd fl ok to pour anop
ELE05-02260 Electrical Rough-In10/6/200510/7/200510/7/2005 9:14:37 AMAPART
Scheduled by a contractor via Hello! on 10/6/2005 at 3:02:09 PM. upper level wall ok to cover anop
ELE05-03611 Permanent Service10/6/200510/7/200510/7/2005 9:12:45 AMAPASS
lana; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr made, p/s o/h re-connect ok
ELE05-03591 Electrical Rough-In10/6/200510/7/200510/7/2005 8:42:31 AMAPART
Scheduled by a contractor via Hello! on 10/6/2005 at 3:58:23 PM. Contact: ###-####. wall cover only break room, office area anop. need to see bath switches, ok to 1 side bath walls only.
ELE05-03583 Temporary Service10/7/200510/7/200510/7/2005 8:37:36 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corrections made, t/s u/g n ok