FIR05-00474
| INSP-Final Inspection | 10/7/2005 | 10/7/2005 | 10/7/2005 5:26:22 PM | P | PASS |
|
|
Hood suppression system operated correctly under test conditions, alarm reported to the existing panel but did not activate new notification devices in the immediate vicinity due to the pending fire alarm permit work in progress.
|
BLD05-00487
| FIRE-Alarm Testing | 10/7/2005 | 10/7/2005 | 10/7/2005 5:19:09 PM | P | FAIL |
|
|
Provide fire ext. with current inspection tag, provide max occupant load sign, relocate K class extinguisher as discussed, need to final fire sprinkler permit prior to bld final.
|
FIR05-00619
| INSP-Final Inspection | 10/7/2005 | 10/7/2005 | 10/7/2005 3:09:17 PM | A | PASS |
|
|
Fire sprinkler permitted work passed inspection. Main control and riser supervision to be completed under the fire alarm permit fir05-00587 work in progress.
|
MIS05-00179
| FIR-Final | 10/7/2005 | 10/7/2005 | 10/7/2005 2:38:03 PM | P | FAIL |
|
|
Provide sign above main entry/exit door stating "this door to remain unlocked while building is occupied", provide current inspection tag and mount fire extinguisher on the wall as discussed.
|
FIR05-00316
| INSP-Final Inspection | 10/7/2005 | 10/7/2005 | 10/7/2005 1:34:12 PM | P | CANC |
|
|
Inspection to be rescheduled for monday the 10th per agreement with Rick Jackson. Sufficient information to determine what has and has not been tested is not available to a degree that is comfortable for verification without being familiar with the project history. This inspection to be defered to Troy Cobbley per request by Forrest.
|
FIR05-00385
| INSP-Sprinkler Rough-in | 10/7/2005 | 10/7/2005 | 10/7/2005 1:22:42 PM | P | FAIL |
|
|
Upright heads at first floor landings in both stairways are overspaced, upright head is missing above restroom 1st floor, hanger is missing on an armover above restroom 3rd floor, provide resubmittals reflecting added uprights and pipe layout changes at restrooms 1st, 2nd, and 3rd floors.
|
FIR05-00434
| INSP-Final Inspection | 10/6/2005 | 10/7/2005 | 10/7/2005 12:50:04 PM | A | PART |
|
|
Access door with signage and signage for the aux. drain valve in the sw stairwell have been installed as required.
|
BLD04-02996
| FIRE-Final Inspection | 10/6/2005 | 10/7/2005 | 10/7/2005 11:50:44 AM | A | PASS |
|
|
Fire life safety passed inspection.
|
MIS05-00175
| FIR-Final | 10/6/2005 | 10/7/2005 | 10/7/2005 10:59:20 AM | A | FAIL |
|
|
Provide current inspection tag for the fire extinguisher and mount extinguisher as discussed, remove deadbolt at back exit door.
|
FIR05-00614
| INSP-Sprinkler Rough-in/Hydro | 10/7/2005 | 10/7/2005 | 10/7/2005 9:48:58 AM | A | PART |
|
|
Overhead fire sprinkler rough in is good for cover.
|
FIR05-00329
| INSP-Final Inspection | 10/6/2005 | 10/7/2005 | 10/7/2005 9:47:34 AM | A | PASS |
|
|
Fail safe door hardware operation functions properly, fire alarm permit finaled.
|
FIR05-00472
| INSP-Final Inspection | 10/5/2005 | 10/7/2005 | 10/7/2005 8:53:56 AM | A | PASS |
|
|
Items on correction notice have been completed, fire alarm finaled.
|
FIR05-00429
| INSP-Final Inspection | 10/7/2005 | 10/7/2005 | 10/7/2005 12:00:00 AM | P | PART |
|
|
Final pending installation of ceiling tile and escutcheons.
|