Inspections for the day of: Friday, October 7, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00474 INSP-Final Inspection10/7/200510/7/200510/7/2005 5:26:22 PMPPASS
Hood suppression system operated correctly under test conditions, alarm reported to the existing panel but did not activate new notification devices in the immediate vicinity due to the pending fire alarm permit work in progress.
BLD05-00487 FIRE-Alarm Testing10/7/200510/7/200510/7/2005 5:19:09 PMPFAIL
Provide fire ext. with current inspection tag, provide max occupant load sign, relocate K class extinguisher as discussed, need to final fire sprinkler permit prior to bld final.
FIR05-00619 INSP-Final Inspection10/7/200510/7/200510/7/2005 3:09:17 PMAPASS
Fire sprinkler permitted work passed inspection. Main control and riser supervision to be completed under the fire alarm permit fir05-00587 work in progress.
MIS05-00179 FIR-Final10/7/200510/7/200510/7/2005 2:38:03 PMPFAIL
Provide sign above main entry/exit door stating "this door to remain unlocked while building is occupied", provide current inspection tag and mount fire extinguisher on the wall as discussed.
FIR05-00316 INSP-Final Inspection10/7/200510/7/200510/7/2005 1:34:12 PMPCANC
Inspection to be rescheduled for monday the 10th per agreement with Rick Jackson. Sufficient information to determine what has and has not been tested is not available to a degree that is comfortable for verification without being familiar with the project history. This inspection to be defered to Troy Cobbley per request by Forrest.
FIR05-00385 INSP-Sprinkler Rough-in10/7/200510/7/200510/7/2005 1:22:42 PMPFAIL
Upright heads at first floor landings in both stairways are overspaced, upright head is missing above restroom 1st floor, hanger is missing on an armover above restroom 3rd floor, provide resubmittals reflecting added uprights and pipe layout changes at restrooms 1st, 2nd, and 3rd floors.
FIR05-00434 INSP-Final Inspection10/6/200510/7/200510/7/2005 12:50:04 PMAPART
Access door with signage and signage for the aux. drain valve in the sw stairwell have been installed as required.
BLD04-02996 FIRE-Final Inspection10/6/200510/7/200510/7/2005 11:50:44 AMAPASS
Fire life safety passed inspection.
MIS05-00175 FIR-Final10/6/200510/7/200510/7/2005 10:59:20 AMAFAIL
Provide current inspection tag for the fire extinguisher and mount extinguisher as discussed, remove deadbolt at back exit door.
FIR05-00614 INSP-Sprinkler Rough-in/Hydro10/7/200510/7/200510/7/2005 9:48:58 AMAPART
Overhead fire sprinkler rough in is good for cover.
FIR05-00329 INSP-Final Inspection10/6/200510/7/200510/7/2005 9:47:34 AMAPASS
Fail safe door hardware operation functions properly, fire alarm permit finaled.
FIR05-00472 INSP-Final Inspection10/5/200510/7/200510/7/2005 8:53:56 AMAPASS
Items on correction notice have been completed, fire alarm finaled.
FIR05-00429 INSP-Final Inspection10/7/200510/7/200510/7/2005 12:00:00 AMPPART
Final pending installation of ceiling tile and escutcheons.