Inspections for the day of: Tuesday, October 7, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00247 INSP-Final Inspection10/6/200810/7/200810/8/2008 4:40:54 PMPPASS
Fire alarm permit finaled.
FIR08-00133 INSP-Final Inspection10/6/200810/7/200810/8/2008 4:40:26 PMPPASS
Fire alarm permit finaled.
FIR08-00132 INSP-Final Inspection10/6/200810/7/200810/8/2008 4:40:04 PMPPASS
Fire alarm permit finaled.
FIR06-00620 INSP-Alarm Testing10/3/200810/7/200810/7/2008 5:38:28 PMAPART
Inspection completed for cleanroom area ceiling mounted heat detectors only, need to provide accurate addressing at plenum #5, install one missing junction box cover. Intelligent detectors not tested at this time.
FIR08-00436 FIR-Aging Inspection10/7/200810/7/200810/7/2008 5:33:05 PM DONE
Work in progress, construction underway.
FIR08-00371 INSP-Final Inspection10/6/200810/7/200810/7/2008 1:34:04 PMPCANC
darsey Phone #: ###-####
FIR08-00640 INSP-Sprinkler Rough-in/Hydro10/6/200810/7/200810/7/2008 1:33:28 PMANR
bruce Phone #: ###-#### Inspection to be rescheduled per conversation with contractor.
FIR07-01051 INSP-Sprinkler Rough-in10/6/200810/7/200810/7/2008 1:31:33 PMAPART
Overhead rough-in for areas D and E 1st floor as red lined with todays date are approved except as noted on plans sheet 6 and 7. Items include adding missing coverage at the mechanical room/chase between the restrooms, provide sway bracing at the end mains per NFPA 13 2007 9.3.5.3.4, noted two missing hangers, pipe hangers above hard lid ceilings below the stairways and at the mechanical room okayed.