FIR09-00519
| INSP-Final Inspection | 10/7/2009 | 10/7/2009 | 10/7/2009 5:00:38 PM | P | NR |
|
|
Final pending missing ceiling tile and escutcheons.
|
BLD09-01425
| FIRE-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 4:59:38 PM | A | PASS |
|
|
Fire life safety final okay pending installation of one fire extinguisher, post max occupant load sign, repair one EM light at the back exit corridor. Items to be done prior to structural final approval.
|
FIR09-00498
| INSP-Final Inspection | 10/5/2009 | 10/7/2009 | 10/7/2009 4:54:37 PM | A | PASS |
|
|
Scope of fire alarm permit work passed inspection, permit finaled.
|
FIR09-00413
| INSP-Sprinkler Rough-in | 10/6/2009 | 10/7/2009 | 10/7/2009 1:53:17 PM | A | PART |
|
|
Remainder of overhead work okayed for cover with the exception of two locations clouded on plans including the one upright at the server room to be relocated and an overspaced head due to floorplan changes at the locker area.
|
FIR09-00576
| INSP-Final Inspection | 10/7/2009 | 10/7/2009 | 10/7/2009 1:49:45 PM | A | PASS |
|
|
Fire alarm system modifications passed field testing, okay for final.
|
FIR09-00569
| INSP-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 1:48:36 PM | A | PASS |
|
|
Hood suppression systems operated correctly under test conditions, contractor to provide a current certification for the K class extinguisher-will be verified at fire life safety final, open junction boxes covered while on site, inspection passed and permit finaled.
|
BLD09-01676
| FIRE-Final Inspection | 10/5/2009 | 10/7/2009 | 10/7/2009 1:45:55 PM | A | PASS |
|
|
Life safety passed. Note to structural inspector: please verify the fire extinguisher is provided with a current certification tag- tenant to have completed prior to final.
|