BLD09-01547
| FIRE-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 4:33:47 PM | P | FAIL |
|
|
Fire sprinkler coverage needs modified around where the hood was previously located. All other items are ok.
|
FIR09-00590
| INSP-Final Inspection | 10/7/2009 | 10/7/2009 | 10/7/2009 3:20:05 PM | P | PASS |
|
|
Permit finaled
|
BLD09-01250
| FIRE-Final Inspection | 10/7/2009 | 10/7/2009 | 10/7/2009 3:10:51 PM | P | PASS |
|
|
life safety passed
|
FIR09-00584
| INSP-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 3:09:18 PM | P | PASS |
|
|
Permit finaled.
|
FIR07-01031
| INSP-Final Inspection | 10/7/2009 | 10/7/2009 | 10/7/2009 3:08:19 PM | P | PASS |
|
|
permit finaled
|
BLD09-01367
| FIRE-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 3:07:19 PM | A | FAIL |
|
|
Todays inspection was just for the remaining portion of the remodeled east dressing rooms which has passed life safety.
|
BLD07-01846
| FIRE-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 11:17:31 AM | A | FAIL |
|
|
Life safety will be ok to pass when the project related fire alarm and fire sprinkler permits are passed.
|
FIR09-00150
| INSP-Final Inspection | 10/5/2009 | 10/7/2009 | 10/7/2009 11:11:11 AM | A | FAIL |
|
|
The module monitoring trouble on the NAC panel has been provided and tested. The 18ah batteries are now added and both sets of approved plans are on site. The EOL voltage is passed on the circuit over the office area of the building. The inspection was stopped from sending additional signals due to the AES panel being at a Netcom 6. It temporarily went to a Netcom 5 but then went back to a 6. Also the sound from the horns on the notification circuit is not sync'd as required per NFPA 72 Chapter 6. Placement of the notification devices appeared to be ok except back in a storage room where the strobe was not placed as per the plan and now coverage is lacking. This device will need to be relocated or an additional device added.
|
BLD07-01834
| FIRE-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 11:04:21 AM | A | PASS |
|
|
Life safety is passed.
|
BLD09-00982
| FIRE-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 9:38:09 AM | A | FAIL |
|
|
Need the ADA hardware for the two pocket doors and the remote annunciator for the duct smoke detector installed and tested.
|
BLD09-01653
| FIRE-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 9:34:43 AM | A | CANC |
|
|
###-#### Refugio//inspection for temp sign off to operate restaurant portion of tenant space. Canceled per telephone conversation.
|
FIR09-00590
| INSP-Alarm Testing | 10/6/2009 | 10/7/2009 | 10/7/2009 8:44:36 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 10/6/2009 at 4:21:40 PM. Contact: ###-####.
|
FIR09-00570
| INSP-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 8:38:08 AM | A | PASS |
|
|
Hood suppression system operated correctly. Lights turned off and the gas shut off.
|
FIR09-00365
| INSP-Final Inspection | 10/6/2009 | 10/7/2009 | 10/7/2009 7:10:31 AM | A | PASS |
|
|
Permit finaled
|