Inspections for the day of: Friday, October 7, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00414 INSP-Sprinkler Rough-in10/7/201110/7/201110/7/2011 4:39:00 PMPPART
Verified corrections, overhead work approved for cover.
FIR11-00542 INSP-Sprinkler Rough-in10/7/201110/7/201110/7/2011 4:27:08 PMPPART
One room as marked and dated on plans is approved for ceiling cover.
FIR11-00194 INSP-Sprinkler Rough-in10/7/201110/7/201110/7/2011 4:26:27 PMPPART
Only clouded areas marked with today's date okayed for cover. Field install does not match plan at the bi-plane room, floorplan has changed, missing coverage at an electrical closet, one head adjacent to a soffit is blocked.
BLD11-02393 FIRE-Final Inspection10/7/201110/7/201110/7/2011 4:23:05 PMPPASS
Fire life safety inspection passed. PFE is due annual certification this month.
FIR11-00483 INSP-Supply line flush10/6/201110/7/201110/7/2011 4:22:01 PMPPART
UG fire supply line flush completed acceptable.
FIR11-00418 INSP-Sprinkler Rough-in10/7/201110/7/201110/7/2011 4:20:56 PMPPART
Overhead modifications at the remodel area okayed for ceiling cover with the exception of one missing head at the file room- to be added and verified at final per discussion.
FIR11-00414 INSP-Sprinkler Rough-in10/6/201110/7/201110/7/2011 4:19:28 PMAFAIL
Overspaced head at the 2nd floor, one pendent head at the 2nd floor and three pendent heads at the 1st floor are too close to light fixture junction boxes.
FIR10-00346 INSP-Final Inspection10/3/201110/7/201110/7/2011 4:16:55 PMAPASS
Corrections and adjustments made while on site. Network capabilities tested satisfactory, re-inspection items passed. Scope of fire alarm permit finaled.