ELE12-01994
| ELE-Aging Inspection | 10/7/2014 | 10/7/2014 | 10/8/2014 7:41:14 AM | | DONE |
|
|
too busy
|
ELE12-01434
| ELE-Aging Inspection | 10/7/2014 | 10/7/2014 | 10/8/2014 7:40:47 AM | | DONE |
|
|
too busy
|
ELE14-02759
| Final | 10/7/2014 | 10/7/2014 | 10/7/2014 5:03:00 PM | P | PASS |
|
|
Matt Phone #: ###-#### final ok
|
ELE14-02759
| Permanent Service | 10/7/2014 | 10/7/2014 | 10/7/2014 5:02:36 PM | P | PASS |
|
|
Matt Phone #: ###-#### p/s o/h rec ok
|
ELE14-02201
| Electrical Rough-In | 10/7/2014 | 10/7/2014 | 10/7/2014 4:43:33 PM | P | PASS |
|
|
undergroung cover & potting - Kevin Phone #: ###-#### r/i ok pottting and u.g. to pool
|
ELE14-01994
| Final | 10/6/2014 | 10/7/2014 | 10/7/2014 4:24:48 PM | P | PASS |
|
|
Call for access if locked. Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
|
ELE14-02578
| Electrical Rough-In | 10/6/2014 | 10/7/2014 | 10/7/2014 3:40:58 PM | P | PASS |
|
|
Please inspect floor heat in upstairs bathroom Phone #: ###-#### Inspection requested via web by Shaun Kirkman r/i ok 17.8 ohms on floor heat
|
ELE14-01849
| Electrical Rough-In | 10/7/2014 | 10/7/2014 | 10/7/2014 3:22:35 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ceilings ok 100% except 2 rooms
|
ELE14-02780
| Electrical Rough-In | 10/7/2014 | 10/7/2014 | 10/7/2014 2:25:55 PM | P | PASS |
|
|
Robert. Exterior Wall Rough-In. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i ok exterior walls Red Sky
|
ELE14-02783
| Final | 10/7/2014 | 10/7/2014 | 10/7/2014 1:58:55 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kevin Cowgill final ok
|
ELE14-02480
| Final | 10/6/2014 | 10/7/2014 | 10/7/2014 1:58:14 PM | P | PASS |
|
|
Please call Jesse Simpson who will meet you on site to go over the job. Phone #: ###-#### Inspection requested via web by Matthew Dunay final ok
|
GCE14-00165
| GCE-Rough-In | 10/7/2014 | 10/7/2014 | 10/7/2014 1:17:42 PM | P | PASS |
|
|
Brian ###-#### please call 30 min advance for access r/i ok
|
ELE14-02772
| Electrical Rough-In | 10/6/2014 | 10/7/2014 | 10/7/2014 12:41:24 PM | A | PASS |
|
|
wall rough in for new customer service area Phone #: ###-#### Inspection requested via web by Shane Lott r/i ok customer service walls
|
ELE14-00738
| Final | 10/6/2014 | 10/7/2014 | 10/7/2014 12:04:10 PM | A | FAIL |
|
|
Tyler Phone #: ###-#### 210.8(A) all 15 and 20 amp receptacles above kitchen countertops shall be GFCI protected.(kitchen and wet bar upst.) 314,20-all outlet boxes shall be 1/4 inch or less from finish surface to face of box.(box extensions needed). lockoffs required for kitchen hood and dishwasher and water heater. 210.12(A)-AFCI protection required for all bedrooms. 406.9(A)-All outside 15 and 20 amp receptacles require weather resistant receptacles. Disconnect switch required at furnace in attic. A/C condensing unit wiring on load side needs to be rated to use outdoors or type "thwn". Install correct "maximum fuse " size for condensing unit. 400.8-120 volt hockey puck fixture cords not permitted to run through cabinets and open splice not allowed. Strap 1 inch conduit feeding garage within 3 foot of termination.
|
ELE14-02759
| Permanent Service | 10/6/2014 | 10/7/2014 | 10/7/2014 10:36:47 AM | A | FAIL |
|
|
Matthew Phone #: ###-#### additional new ground rod required and #4 for waterbond
|
ELE14-02608
| Final | 10/3/2014 | 10/7/2014 | 10/7/2014 10:03:41 AM | A | PASS |
|
|
Please call homeowner when you are en route, and he will meet you there. Eric ###-#### Thank you Inspection requested via web by Louis Keller final ok
|
ELE14-02512
| Electrical Rough-In | 10/7/2014 | 10/7/2014 | 10/7/2014 9:42:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve sellers r/i ok garage
|
GCE14-00160
| GCE-Rough-In Permanent Service | 10/6/2014 | 10/7/2014 | 10/7/2014 9:21:55 AM | A | PASS |
|
|
Daniel ###-#### r/i ok p/s u/g n ok
|
GCE14-00170
| GCE-Rough-In | 10/6/2014 | 10/7/2014 | 10/7/2014 8:45:55 AM | A | PASS |
|
|
Harold ###-#### or ###-#### please call 30 min advance r/i ok switch and outside receptacle in pop out
|