Inspections for the day of: Monday, October 7, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00665 INSP-Sprinkler Rough-in10/7/201910/7/201910/7/2019 3:28:35 PMPPART
The piping above the hardlids is ok to cover. I noted two heads blocked by beams

Richard Clark is the contact for this RTC inspection. We appreciate your help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-01795 FIRE-Final Inspection10/7/201910/7/201910/7/2019 12:58:00 PMPFAIL
Need the emergency dialer replacement permit, FIR19-00467, finaled first, need city approved plans and small documents, need tagged/mounted fire extinguisher, need exit signs in the room and the two paths of egress repaired, possibly need emergency lighting, sprinklers were spaced for the old light hazard conference room but now the room is an ordinary hazard Laundry room, the fire alarm strobes are overspaced from the northeast corner of the room.....ect.


Dennis Phone #: ###-####
FIR19-00475 INSP-Final Inspection10/3/201910/7/201910/7/2019 12:01:47 PMAFAIL
Still need to remove the tape from the heads.

Jon Beazer is the contact. It doesn''t matter what time of day this inspection takes place. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00353 INSP-Sprinkler Rough-in10/7/201910/7/201910/7/2019 10:38:59 AMPPART
The inspection for the second and third floors failed due to the sidewall heads being overspaced. Perm plan review their max spacing is 18'out and 16' to the side. They have been installed 18'-6" from the far wall. What is approved are the hangers for the stand pipe supplies in the east and west stair wells and the short run of 4" to the FDC. Plan modifications will be required for sprinkler modifications to provide the correct coverage. Nick is the contact. Thank you Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR19-00753 INSP-Final Inspection10/7/201910/7/201910/7/2019 10:34:05 AMPPASS
Permit finaled. The suprssion sytem has been removed and not re-installed as per the scope of work. Per the gerneral contractor and the hood suppression contractor the suppression system is not required for the appliance installed.

please call 1 hour prior to inspection Glen at -###-####7 Inspection requested via web by JJ Wallace
FIR19-00325 INSP-Final Inspection10/7/201910/7/201910/7/2019 10:14:45 AMPPASS
Permit finaled
FIR19-00665 INSP-Sprinkler Rough-in10/4/201910/7/201910/7/2019 9:11:22 AMAFAIL
No city approved plans on site. I noted that two heads along the south wall appear to be blocked by two wood beams.
Richard Clark is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus