Inspections for the day of: Friday, October 8, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01313 FIRE-Final Inspection10/7/200410/8/200410/8/2004 12:00:00 AMAPART
A temporary occupancy was given with dave millers permission until the phone lines have been installed and tested and the fire alarm permit is signed off. 10/8/2004 10:05:08 AM
FIR04-00587 INSP-Sprinkler Rough-in10/7/200410/8/200410/8/2004 12:00:00 AMAFAIL
Plans do not match installation. There are multiple pendants off of the same 1" outlet. In one location there were three pendants off of a single outlet. These are pendants that have been modified by the sprinkler contractor. Resubmit plans showing actual piping layout with hydraulic calculations proving existing layout or resubmit plans showing changes required to provide one pendant from one outlet on branchline. 10/8/2004 9:38:45 AM
FIR04-00619 INSP-Sprinkler Rough-in/Hydro10/7/200410/8/200410/8/2004 12:00:00 AMAPART
Piping under roadway is ok to cover. Thrust blocks and beding is not done yet. Will verify this afternoon. 10/8/2004 12:27:16 PM
FIR04-00594 INSP-Final Inspection10/8/200410/8/200410/8/2004 12:00:00 AMAPART
A temporary occupancy was given with dave millers permission until the phone lines are installed and system tested. I received a copy of the work order giving L&K electric authorization to proceed with this work.
FIR04-00521 INSP-Final Inspection10/7/200410/8/200410/8/2004 12:00:00 AMAPASS
Fire sprinkler finaled 10/8/2004 10:22:05 AM
FIR04-00544 INSP-Final Inspection10/8/200410/8/200410/8/2004 12:00:00 AMPPASS
fire sprinkler finaled 10/8/2004 4:00:44 PM
BLD04-01194 FIRE-Final Inspection10/8/200410/8/200410/8/2004 12:00:00 AMPPASS
Fire life safety finaled 10/8/2004 12:23:07 PM
FIR04-00588 INSP-Sprinkler Rough-in/Hydro10/8/200410/8/200410/8/2004 12:00:00 AMPCANC
Sprinkler contractor did not have all piping installed. Side sammy's have been installed incorrectly on the branchlines. Inspection to be called in for monday 10/8/2004 3:09:02 PM
FIR04-00208 INSP-Sprinkler Rough-in/Hydro10/8/200410/8/200410/8/2004 12:00:00 AMPPASS
hydro test passed 10/8/2004 3:05:37 PM
FIR04-00619 INSP-Sprinkler Rough-in/Hydro10/7/200410/8/200410/8/2004 12:00:00 AMPCANC
Contractor to call in new inspection when the rest of the underground has been installed. Trent to provide pictures of the thrust block on the 45. 10/8/2004 3:19:36 PM
BLD03-02636 FIRE-Final Inspection10/6/200410/8/200410/6/2004 4:38:35 PMPCANC
rob; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Disp set to [CANC] by a contractor via Hello! on Oct 6 2004 4:38PM.