BLD04-01313
| FIRE-Final Inspection | 10/7/2004 | 10/8/2004 | 10/8/2004 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given with dave millers permission until the phone lines have been installed and tested and the fire alarm permit is signed off. 10/8/2004 10:05:08 AM
|
FIR04-00587
| INSP-Sprinkler Rough-in | 10/7/2004 | 10/8/2004 | 10/8/2004 12:00:00 AM | A | FAIL |
|
|
Plans do not match installation. There are multiple pendants off of the same 1" outlet. In one location there were three pendants off of a single outlet. These are pendants that have been modified by the sprinkler contractor. Resubmit plans showing actual piping layout with hydraulic calculations proving existing layout or resubmit plans showing changes required to provide one pendant from one outlet on branchline. 10/8/2004 9:38:45 AM
|
FIR04-00619
| INSP-Sprinkler Rough-in/Hydro | 10/7/2004 | 10/8/2004 | 10/8/2004 12:00:00 AM | A | PART |
|
|
Piping under roadway is ok to cover. Thrust blocks and beding is not done yet. Will verify this afternoon. 10/8/2004 12:27:16 PM
|
FIR04-00594
| INSP-Final Inspection | 10/8/2004 | 10/8/2004 | 10/8/2004 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given with dave millers permission until the phone lines are installed and system tested. I received a copy of the work order giving L&K electric authorization to proceed with this work.
|
FIR04-00521
| INSP-Final Inspection | 10/7/2004 | 10/8/2004 | 10/8/2004 12:00:00 AM | A | PASS |
|
|
Fire sprinkler finaled 10/8/2004 10:22:05 AM
|
FIR04-00544
| INSP-Final Inspection | 10/8/2004 | 10/8/2004 | 10/8/2004 12:00:00 AM | P | PASS |
|
|
fire sprinkler finaled 10/8/2004 4:00:44 PM
|
BLD04-01194
| FIRE-Final Inspection | 10/8/2004 | 10/8/2004 | 10/8/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 10/8/2004 12:23:07 PM
|
FIR04-00588
| INSP-Sprinkler Rough-in/Hydro | 10/8/2004 | 10/8/2004 | 10/8/2004 12:00:00 AM | P | CANC |
|
|
Sprinkler contractor did not have all piping installed. Side sammy's have been installed incorrectly on the branchlines. Inspection to be called in for monday 10/8/2004 3:09:02 PM
|
FIR04-00208
| INSP-Sprinkler Rough-in/Hydro | 10/8/2004 | 10/8/2004 | 10/8/2004 12:00:00 AM | P | PASS |
|
|
hydro test passed 10/8/2004 3:05:37 PM
|
FIR04-00619
| INSP-Sprinkler Rough-in/Hydro | 10/7/2004 | 10/8/2004 | 10/8/2004 12:00:00 AM | P | CANC |
|
|
Contractor to call in new inspection when the rest of the underground has been installed. Trent to provide pictures of the thrust block on the 45. 10/8/2004 3:19:36 PM
|
BLD03-02636
| FIRE-Final Inspection | 10/6/2004 | 10/8/2004 | 10/6/2004 4:38:35 PM | P | CANC |
|
|
rob; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Disp set to [CANC] by a contractor via Hello! on Oct 6 2004 4:38PM.
|