FIR07-00322
| FIR-Aging Inspection | 10/8/2007 | 10/8/2007 | 10/8/2007 3:15:12 PM | | DEFR |
|
|
wip
|
FIR07-00425
| INSP-Sprinkler Rough-in/Hydro | 10/8/2007 | 10/8/2007 | 10/8/2007 3:14:41 PM | P | PART |
|
|
OH hydrostatic re-test of the 3rd floor passed inspection, also verified DSW heads at the 4th floor patios.
|
FIR07-00655
| INSP-Final Inspection | 10/8/2007 | 10/8/2007 | 10/8/2007 3:13:13 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00655
| INSP-Alarm Testing | 10/5/2007 | 10/8/2007 | 10/8/2007 12:53:35 PM | A | PASS |
|
|
Items on correction notice issued 10/4 re-tested and verified for compliance, inspection passed, noted dust control has not been provided as agreed to by the contractor.
|
FIR07-00765
| INSP-Sprinkler Rough-in | 10/5/2007 | 10/8/2007 | 10/8/2007 12:49:36 PM | A | PART |
|
|
Plans on site, overhead install is approved for cover at the drop ceilings.
|
BLD06-03514
| FIRE-Final Inspection | 10/2/2007 | 10/8/2007 | 10/8/2007 12:48:49 PM | A | FAIL |
|
|
Missing building address numbers, remove the manual thumbturn at the main entry/exit door and provide signage above the door, post PFE's as discussed , provide one additional fire extinguisher for the stock area, need to test EM lighting, remove the deadbolt at the back office door, provide access and facilitate testing of indicated duct smoke detectors for RTU 1 and 2, provide FD access lane marking per fire code review notes for 29th street, approved plans and notes must be on site at all times per condition of the permit.
|