Inspections for the day of: Monday, October 8, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00758 INSP-Final Inspection10/5/200710/8/200710/9/2007 3:22:40 PMPFAIL
This permit was used to call in an inspection for the seafood area. This is not the permit for the seafood area. The fire sprinkler contractor needs to call in the correct permit.
FIR05-00536 INSP-Sprinkler Rough-in10/8/200710/8/200710/8/2007 4:59:30 PMPPASS
The south half of the 9th floor is ok to cover.
FIR07-00800 INSP-Sprinkler Rough-in10/8/200710/8/200710/8/2007 3:42:30 PMPFAIL
No approvied plans on site for the inspection.
BLD07-00018 FIRE-Final Inspection10/5/200710/8/200710/8/2007 3:25:17 PMAFAIL
No approved plans on site.
BLD07-01452 FIRE-Final Inspection10/5/200710/8/200710/8/2007 3:24:23 PMAFAIL
No life safety inspection performed until the related fire alarm permit is finaled. The fire alarm inspection was failed.
BLD07-00948 FIRE-Conference10/6/200710/8/200710/8/2007 3:23:26 PMADONE
Conference was for the life safety requirements in the new garden area.
FIR07-00654 INSP-Alarm Testing10/4/200710/8/200710/8/2007 1:19:34 PMAFAIL
The first duct smoke detector tested did not shut down the unit. The second duct detector was mounted incorrectly. The test was stopped.
BLD07-02286 FIRE-Final Inspection10/2/200710/8/200710/8/2007 12:06:02 PMAPART
A temporary occupancy was given until the fire extinguishers are tagged and the emergency light on the west wall is repaired.
FIR07-00477 INSP-Final Inspection10/5/200710/8/200710/8/2007 10:15:06 AMAPASS
The hydro test on the new system passed and the overhead inspection passed except in the existing area/expansion needs three additional heads due to overspacing off of the wall.