Inspections for the day of: Wednesday, October 8, 2008.
Number of inspections: 33
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00429 ELE-Aging Inspection10/8/200810/8/200810/13/2008 3:51:28 PM DONE
called contractor to schedule an inspection if they are ready, told to verify if ground lugs terminated to in light poles, no esc this project
ELE07-00375 ELE-Aging Inspection10/8/200810/8/200810/13/2008 9:29:36 AM DONE
see final, no esc this project
ELE08-01858 Electrical Rough-In10/8/200810/8/200810/8/2008 4:07:54 PMPPASS
Scheduled by a contractor via Hello! on 10/8/2008 at 9:45:27 AM. Contact: ###-####. ric ok
ESC08-00572 General Inspection10/8/200810/8/200810/8/2008 3:55:03 PMPPASS
looked ok
ESC07-00003 General Inspection10/8/200810/8/200810/8/2008 3:54:13 PMPPASS
looked ok
ESC08-00421 General Inspection10/8/200810/8/200810/8/2008 3:53:10 PMPPASS
looked ok
ESC06-01299 General Inspection10/8/200810/8/200810/8/2008 3:52:22 PMPPASS
looked ok
ESC08-00539 General Inspection10/8/200810/8/200810/8/2008 3:51:21 PMPPASS
looked ok
ESC08-00781 General Inspection10/8/200810/8/200810/8/2008 3:50:25 PMAPASS
looked ok
ESC08-00212 General Inspection10/8/200810/8/200810/8/2008 3:49:37 PMAPASS
looked ok
ESC07-00733 General Inspection10/8/200810/8/200810/8/2008 3:48:39 PMAPASS
looked ok
ESC07-00199 General Inspection10/8/200810/8/200810/8/2008 3:47:38 PMAPASS
looked ok
ESC08-00730 General Inspection10/8/200810/8/200810/8/2008 3:43:37 PMAPASS
looked ok
ELE08-02678 Electrical Rough-In10/8/200810/8/200810/8/2008 3:42:19 PMPPASS
contact" John Ostolasa - ceiling insp. late afternoon inspection if possible. Also please call before going so John can let you in Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover ceiling, no esc this project
ELE08-02738 Rough-In Permanent Service10/8/200810/8/200810/8/2008 3:09:07 PMPPASS
eric Phone #: ###-#### ric ok, p/s u/g n ok
ELE08-02719 Final10/6/200810/8/200810/8/2008 2:37:30 PMPCANC
Try to schedule after 3:330pm If you have any questions please contact Francis@###-#### or ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose wrong type request see p/s
ELE08-02719 Permanent Service10/8/200810/8/200810/8/2008 2:29:04 PMPPASS
Try to schedule after 3:330pm If you have any questions please contact Francis@###-#### or ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose p/s o/h rec ok, no esc this project
ELE07-02302 Final10/8/200810/8/200810/8/2008 2:27:16 PMPPART
Contact Steve Hess - area A final please Phone #: ###-#### Internet Inspection Request from: Deb Gooden signed t/o card for auditorium, area a, left correction notice that stage lighting must be programmed before final
ELE07-03307 Electrical Rough-In10/8/200810/8/200810/8/2008 2:10:34 PMPPASS
CONTACT: NEIL RAMSEY - ABOVE CEILING INSPECTION FOR THE EAST PORTION OF 4TH FLOOR Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover 4th floor floor ceilings
ELE08-02171 Final10/8/200810/8/200810/8/2008 1:35:30 PMPFAIL
stu Phone #: ###-#### met contractor, left correction notice, NEC 410.10(D) luminaires in shower area shall be listed for damp locations, BCC no violations shall be retained
ELE08-02619 Final10/8/200810/8/200810/8/2008 1:32:32 PMPPASS
Pat there were some details that we talked about before you went on vacation. This is the one that you said could be inspected without interior access. Thanks
Phone #: ###-#### Internet Inspection Request from: Jamie Winters called contractor, ok to final, no esc this project
ELE08-01580 Final10/7/200810/8/200810/8/2008 11:52:39 AMACANC
Final Inspection. Please call Rick Sendra @ ###-#### 30 minutes prior to inspection to gain entry. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson talked with contractor, will reschedule for am tomorrow
ELE08-02740 Rough-In Permanent Service10/8/200810/8/200810/8/2008 11:39:11 AMPCANC
ufer ground Phone #: ###-#### Internet Inspection Request from: Don Lustig wrong type request, see ri
ELE08-02740 Electrical Rough-In10/8/200810/8/200810/8/2008 11:38:42 AMPPASS
ufer ground Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to pour concrete encased electrode
ELE08-02667 Electrical Rough-In10/7/200810/8/200810/8/2008 11:16:43 AMAPASS
butch Phone #: ###-####called left message left survey, NEC 210.52(D) shall provide receptacle within 3' of bath sink, 210.11(C)(3) bath receptacle shall be supplied by 20a circuit with no other outlets, 210.52(A)(1) receptacle shall be installed such that no point is over 6' from receptacle in wall line, ric ok, no green sticker left, talked with contractor
ELE08-02521 Electrical Rough-In10/8/200810/8/200810/8/2008 10:41:08 AMAPASS
Ceiling rough-in. Mid to late morning would be ideal. Phone #: ###-#### Internet Inspection Request from: Dan Wright ok to cover ceiling, no esc this project
ELE08-00376 Electrical Rough-In10/7/200810/8/200810/8/2008 10:21:34 AMAPASS
tom Phone #: ###-#### corrections made, ric ok, no esc this project
ELE08-01858 Electrical Rough-In10/7/200810/8/200810/8/2008 9:50:46 AMANH
John Phone #: ###-#### called contractor, no access, left card
ELE08-02676 Conference10/7/200810/8/200810/8/2008 9:33:22 AMADONE
Please meet Brian Keith at Property at 9 a.m. Wednesday. Thanks. Phone #: ###-#### Internet Inspection Request from: Clint Tate met contractor to review requirements to bring park up to code, no esc this project
ELE07-02082 Conference10/7/200810/8/200810/8/2008 8:53:59 AMADONE
steve Phone #: ###-#### met with owner, talked about t/s and using existing direct burial cable from ipco to feed temp pole. Talked about if mounting secure for t/s, said would probably work as mounted
ELE08-02724 Electrical Rough-In10/7/200810/8/200810/8/2008 8:28:35 AMAPASS
Rocky- cover Phone #: ###-#### ric ok
ELE08-02732 Electrical Rough-In10/7/200810/8/200810/8/2008 8:00:50 AMAPASS
Requesting approval for wall cover in all office areas. Phone #: ###-#### Internet Inspection Request from: Lloyd Looney called contractor, ric ok walls only
ELE08-02738 Electrical Rough-In10/8/200810/8/200810/8/2008 12:00:00 AMPDONE
eric Phone #: ###-####