Inspections for the day of: Wednesday, October 8, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00612 INSP-Sprinkler Rough-in/Hydro10/7/200810/8/200810/8/2008 4:37:48 PMPFAIL
Lacking coverage at both the north and south stairway landings 1st floor, seismic bracing at two locations is not approved including at the riser and the 3rd floor. See locations marked on plans.
FIR08-00437 FIR-Aging Inspection10/8/200810/8/200810/8/2008 4:34:01 PM DONE
Work in progress, construction underway.
FIR08-00279 INSP-Conference10/7/200810/8/200810/8/2008 4:32:16 PMPDONE
Conference regarding attatched outside storage area. See NFPA 13 2007 8.15.7.5 regarding coverage at areas below exterior canopies.
FIR08-00650 INSP-Final Inspection10/7/200810/8/200810/8/2008 4:29:34 PMAPASS
Interconnections at the clean agent system to the fire alarm control panel including off site monitoring verified, permit finaled.
FIR07-01018 INSP-Final Inspection10/7/200810/8/200810/8/2008 4:27:26 PMAPASS
Items on C/N finished, forward flow testing passed, outside bell adjusted while on site, overhead fire sprinkler permit finaled.
FIR08-00364 INSP-Final Inspection10/6/200810/8/200810/8/2008 4:25:14 PMAPART
Permit cannot be finaled at this time due to non-functional HVAC units. FACP, batteries, phone lines, and sprinkler monitoring tested okay, one flow switch adjusted while on site, signals verified.
FIR06-00621 INSP-Alarm Testing10/3/200810/8/200810/8/2008 4:22:30 PMAPART
Tested remainder of heat detection devices in building 2 at the non-clean common corridors and mechanical areas.
FIR08-00279 INSP-Conference10/7/200810/8/200810/7/2008 2:59:28 PMPCANC
Mike Bierman is the contact. Thanks. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus