FIR09-00510
| FIR-Aging Inspection | 10/8/2012 | 10/8/2012 | 10/10/2012 8:05:55 AM | | NR |
|
|
I spoke to Matt and he is going to get me the contact information for Consolidated Fire.
|
FIR12-00395
| INSP-Sprinkler Rough-in | 10/8/2012 | 10/8/2012 | 10/8/2012 3:46:28 PM | P | PASS |
|
|
Third floor sprinkler piping can be covered. Tenting has been repaired.
|
FIR12-00078
| INSP-Final Inspection | 9/25/2012 | 10/8/2012 | 10/8/2012 3:29:16 PM | A | CANC |
|
|
Rescheduled for tomorrow.
|
FIR12-00395
| INSP-Sprinkler Rough-in/Hydro | 10/8/2012 | 10/8/2012 | 10/8/2012 3:24:53 PM | P | FAIL |
|
|
Overhead hydro test for all three systems failed.Performed the test twice.
|
FIR12-00531
| INSP-Supply line flush | 10/8/2012 | 10/8/2012 | 10/8/2012 3:23:51 PM | P | PASS |
|
|
The center section as shown on the approved plans is ok to cover. Also the underground supply line flush passed.
|
BLD12-00550
| FIRE-Final Inspection | 10/5/2012 | 10/8/2012 | 10/8/2012 1:58:57 PM | A | FAIL |
|
|
Remove the thumbturn dead bolt from the main exit (keyed is ok), replace the broken electrical cover at the sign, sprinkler heads are overspaced and need to be modified (this work requires a separate permit), provide access to the fire sprinkler riser room to verify annual inspection, repair exit signs and emergency lighting.
|
BLD12-01393
| FIRE-Final Inspection | 10/5/2012 | 10/8/2012 | 10/8/2012 11:02:12 AM | A | PASS |
|
|
Life safety passed. Inspector Jim Sly verified the installation of the insulation in the combustible concealed spaces. See previous inspection entrys.
|
FIR12-00560
| INSP-Sprinkler Rough-in | 10/5/2012 | 10/8/2012 | 10/8/2012 9:57:49 AM | A | PASS |
|
|
Sprinkler rough-in passed. piping can be covered.
|
FIR12-00531
| INSP-Sprinkler Rough-in | 10/4/2012 | 10/8/2012 | 10/8/2012 8:36:17 AM | A | PASS |
|
|
See the city approved plans for two of the three shown locations where the underground supply line can be covered. Per contractor mechanical restraints are being used at the fittings. As-builts are required showing the 6" pipe instead of the 8".
|