Inspections for the day of: Tuesday, October 8, 2013.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00695 INSP-Sprinkler Rough-in/Hydro10/8/201310/8/201310/8/2013 3:44:43 PMPCANC
hyro test // Kerry Phone #: ###-####
BLD13-02688 FIRE-Final Inspection10/7/201310/8/201310/8/2013 3:10:16 PMAFAIL
Provide resubmittals showing the actual wall layout. Provide verification the fire doors are required. If required they need to meet the activation requirements of IBC. If not required they can remain. Repair the exit signs. Repair or remove the emergency lighting. Provide a permit for the fire alarm modifications or for the removal of the fire alarm system. Remove the deadbolts from the doors and provide single action hardware on all exterior doors except the main exit.
BLD12-03195 FIRE-Final Inspection10/8/201310/8/201310/8/2013 2:59:42 PMPPART
A temporary occupancy is given with scotts permission until fire dept access signage is provided.
FIR12-00695 INSP-Sprinkler Rough-in10/7/201310/8/201310/8/2013 2:15:55 PMAPASS
See the city approved plans for locations with todays date where additional piping is ok to cover.
BLD13-01138 FIRE-Final Inspection10/8/201310/8/201310/8/2013 2:14:55 PMPPASS
Life safety passed
BLD13-02643 FIRE-Final Inspection10/8/201310/8/201310/8/2013 2:13:33 PMPPASS
life safety passed
BLD13-02474 FIRE-Final Inspection10/7/201310/8/201310/8/2013 12:53:44 PMAPASS
life safety passed
FIR13-00442 INSP-Final Inspection10/7/201310/8/201310/8/2013 9:32:38 AMAFAIL
Gas turned off but the power failed to turn off.
BLD13-02643 FIRE-Final Inspection10/7/201310/8/201310/8/2013 9:09:34 AMAFAIL
I left a voice message on the contacts phone that I was on the way. I arrived at the job site and was locked up with no access. No inspection was performed. ayad Phone #: ###-####