ELE13-01262
| ELE-Aging Inspection | 10/8/2015 | 10/8/2015 | 10/12/2015 2:18:59 PM | | DONE |
|
|
Called contractor they will check on job for access and call for final.
|
ELE15-02615
| Electrical Rough-In | 10/7/2015 | 10/8/2015 | 10/8/2015 3:07:36 PM | P | PASS |
|
|
Rough for 4 dental stations Phone #: ###-#### Inspection requested via web by Zane Robertson Floor receptacle outlets fed with ENT. Made note on correction from previous inspection to remove power cords that have been fished down interior wall and to refeed floor boxes for dental chairs with an approved method. Walls and patches rough in ok cover
|
ELE15-03146
| Electrical Rough-In | 10/8/2015 | 10/8/2015 | 10/8/2015 2:36:32 PM | P | PASS |
|
|
underground; Jimmy Phone #: ###-#### Parking lot underground to pole bases and N.W corner and spare to N.E. Rough in ok cover
|
ELE15-00180
| Final | 10/8/2015 | 10/8/2015 | 10/8/2015 2:12:39 PM | P | FAIL |
|
|
garage code 0813 Phone #: ###-#### Inspection requested via web by cal crosby 314.21- Garage drywall shall be repaired around boxes so no gap around box exceeds 1/8". *Mis-wire in kitchen and dining boxes. 3-way for kitchen lights locks out power to dining light. 440.6(A)- Max overcurrent device 25 amp on nameplate 30 amp installed.
|
ELE15-03117
| Electrical Rough-In | 10/8/2015 | 10/8/2015 | 10/8/2015 1:13:57 PM | P | PASS |
|
|
UNDERGROUND Inspection, please. Chad Van Orden is contact at ###-####. thank you Phone #: ###-#### Inspection requested via web by Debby Pierce Underslab low volt and 2 stub each side of entrance rough in ok cover
|
ELE15-02329
| Final | 10/8/2015 | 10/8/2015 | 10/8/2015 12:46:13 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dustin Kuester Final ok
|
ELE15-02598
| Electrical Rough-In | 10/7/2015 | 10/8/2015 | 10/8/2015 11:51:28 AM | A | FAIL |
|
|
Rough inspection of phase-2 back hallway of Customer Service. Phone #: ###-#### Inspection requested via web by Richard Montgomery No description of area under construction, unable to located work being performed contacted contractor they will reschedule when someone figures out where to inspect.
|
ELE15-01812
| Electrical Rough-In | 10/7/2015 | 10/8/2015 | 10/8/2015 11:22:59 AM | A | PASS |
|
|
underground; Tate Phone #: ###-#### Underground south to vac stations and west to pole lights and sign. Rough in ok cover
|
ELE15-03246
| Final | 10/7/2015 | 10/8/2015 | 10/8/2015 10:35:40 AM | A | PASS |
|
|
Joe ###-#### Final ok
|
ELE15-03253
| Electrical Rough-In | 10/8/2015 | 10/8/2015 | 10/8/2015 10:17:01 AM | A | PASS |
|
|
Please call half an hour before inspection to insure access. Thanks Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Kitchen remodel rough in ok cover
|
ELE14-03277
| Final | 10/7/2015 | 10/8/2015 | 10/8/2015 10:04:07 AM | A | PASS |
|
|
this should have been finaled a long time ago Phone #: ###-#### Inspection requested via web by ron spen cer Temp service job completed final ok
|
ELE15-02431
| Final | 10/7/2015 | 10/8/2015 | 10/8/2015 9:27:22 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer 110.3(B)- Receptacles shall be installed to manufactured instructions. Reverse polarity front bed. 200.7- Grounded conductor used as ungrounded conductor shall be identified other than white at panel and AC disconnect. 210.8(A)(7)- Receptacle outlets installed with 6' of a sink shall have GFCI protection. 314.25- In complete installations each box shall have a cover. Range box. 352.30(A)- Service riser. PVC shall be secured within 3' of meter enclosure.
|
ELE15-03026
| Permanent Service | 10/7/2015 | 10/8/2015 | 10/8/2015 8:36:26 AM | A | PASS |
|
|
Lockbox code 2630 Phone #: ###-#### Inspection requested via web by Eric Schroeder Circuit directory shall be completed for final. p/s u/g rec ok
|
ELE15-03246
| Permanent Service | 10/7/2015 | 10/8/2015 | 10/7/2015 3:36:54 PM | A | PASS |
|
|
Joe Phone #: ###-#### Ground rod and plumbing bond exists from existing service. Will verify work AM thurday. p/s u/g rec ok
|