Inspections for the day of: Thursday, October 8, 2015.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01262 ELE-Aging Inspection10/8/201510/8/201510/12/2015 2:18:59 PM DONE
Called contractor they will check on job for access and call for final.
ELE15-02615 Electrical Rough-In10/7/201510/8/201510/8/2015 3:07:36 PMPPASS
Rough for 4 dental stations Phone #: ###-#### Inspection requested via web by Zane Robertson Floor receptacle outlets fed with ENT. Made note on correction from previous inspection to remove power cords that have been fished down interior wall and to refeed floor boxes for dental chairs with an approved method. Walls and patches rough in ok cover
ELE15-03146 Electrical Rough-In10/8/201510/8/201510/8/2015 2:36:32 PMPPASS
underground; Jimmy Phone #: ###-#### Parking lot underground to pole bases and N.W corner and spare to N.E. Rough in ok cover
ELE15-00180 Final10/8/201510/8/201510/8/2015 2:12:39 PMPFAIL
garage code 0813 Phone #: ###-#### Inspection requested via web by cal crosby 314.21- Garage drywall shall be repaired around boxes so no gap around box exceeds 1/8".
*Mis-wire in kitchen and dining boxes. 3-way for kitchen lights locks out power to dining light.
440.6(A)- Max overcurrent device 25 amp on nameplate 30 amp installed.
ELE15-03117 Electrical Rough-In10/8/201510/8/201510/8/2015 1:13:57 PMPPASS
UNDERGROUND Inspection, please. Chad Van Orden is contact at ###-####. thank you Phone #: ###-#### Inspection requested via web by Debby Pierce Underslab low volt and 2 stub each side of entrance rough in ok cover
ELE15-02329 Final10/8/201510/8/201510/8/2015 12:46:13 PMPPASS
Phone #: ###-#### Inspection requested via web by Dustin Kuester Final ok
ELE15-02598 Electrical Rough-In10/7/201510/8/201510/8/2015 11:51:28 AMAFAIL
Rough inspection of phase-2 back hallway of Customer Service. Phone #: ###-#### Inspection requested via web by Richard Montgomery No description of area under construction, unable to located work being performed contacted contractor they will reschedule when someone figures out where to inspect.
ELE15-01812 Electrical Rough-In10/7/201510/8/201510/8/2015 11:22:59 AMAPASS
underground; Tate Phone #: ###-#### Underground south to vac stations and west to pole lights and sign. Rough in ok cover
ELE15-03246 Final10/7/201510/8/201510/8/2015 10:35:40 AMAPASS
Joe ###-#### Final ok
ELE15-03253 Electrical Rough-In10/8/201510/8/201510/8/2015 10:17:01 AMAPASS
Please call half an hour before inspection to insure access. Thanks Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Kitchen remodel rough in ok cover
ELE14-03277 Final10/7/201510/8/201510/8/2015 10:04:07 AMAPASS
this should have been finaled a long time ago Phone #: ###-#### Inspection requested via web by ron spen cer Temp service job completed final ok
ELE15-02431 Final10/7/201510/8/201510/8/2015 9:27:22 AMAFAIL
Phone #: ###-#### Inspection requested via web by ron spen cer
110.3(B)- Receptacles shall be installed to manufactured instructions. Reverse polarity front bed.
200.7- Grounded conductor used as ungrounded conductor shall be identified other than white at panel and AC disconnect.
210.8(A)(7)- Receptacle outlets installed with 6' of a sink shall have GFCI protection.
314.25- In complete installations each box shall have a cover. Range box.
352.30(A)- Service riser. PVC shall be secured within 3' of meter enclosure.
ELE15-03026 Permanent Service10/7/201510/8/201510/8/2015 8:36:26 AMAPASS
Lockbox code 2630 Phone #: ###-#### Inspection requested via web by Eric Schroeder Circuit directory shall be completed for final. p/s u/g rec ok
ELE15-03246 Permanent Service10/7/201510/8/201510/7/2015 3:36:54 PMAPASS
Joe Phone #: ###-#### Ground rod and plumbing bond exists from existing service. Will verify work AM thurday. p/s u/g rec ok