Inspections for the day of: Tuesday, October 8, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03474 Electrical Rough-In10/8/201910/8/201910/8/2019 3:01:25 PMPPASS
underground inspection. Phil is the contact Phone #: ###-#### Inspection requested via web by Deb Ipsen Conduits ran Along Street / sidewalk. ok to cover
ELE19-03834 Conference10/7/201910/8/201910/8/2019 2:42:03 PMPPASS
Prefer after 2pm if possible Phone #: ###-#### Inspection requested via web by Paul Stewart talked about moving a/c disc. Conduit will be ran 18in under pavers. A/C is 23.5A min and 40A max. 10awg in conduit to new disc. location. owner has done work before and is aware of inspection process
ELE19-01948 Permanent Service10/8/201910/8/201910/8/2019 1:52:54 PMPPART
Service inspection and review areas that are complete and ready for occupancy Phone #: ###-#### Inspection requested via web by Jason Parke 110.26C3. Personnel doors. Where equipment rated 800A or more that contain overcurrent devices. Personel doors shall open in the direction of egress and be equiped with listerd panic hardware.. (Bus duct electrical room.) NE and SE area cubicals checked and ready for final.
ELE19-01784 Electrical Rough-In10/8/201910/8/201910/8/2019 12:45:08 PMPPASS
light pole bases // Mark Phone #: ###-#### 4 pole bases only ok to cover
ELE19-03817 Electrical Rough-In10/7/201910/8/201910/8/2019 11:31:46 AMAPASS
street light conduit, cage and grounding inspection prior to concrete. Phone #: ###-#### Inspection requested via web by michael hunt Pole base only ok to cover
ELE19-03744 Rough-In Permanent Service10/8/201910/8/201910/8/2019 11:15:26 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson rough in ok p/s u/g n ok
ELE19-03743 Rough-In Permanent Service10/8/201910/8/201910/8/2019 11:14:51 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson rough in ok p/s u/g n ok
ELE19-01631 Final10/7/201910/8/201910/8/2019 10:26:19 AMANR
If you can give me a heads up. Around 30 minutes prior before heading over I will have somebody meet you there. Thank you. Phone #: ###-#### Inspection requested via web by David Kubik Not ready. Spoke to contractor. Needed to install breaker lockout and AFCI recep for master bedroom.
ELE19-03420 Electrical Rough-In10/7/201910/8/201910/8/2019 9:18:13 AMAPASS
phase 2 // Jose Phone #: ###-#### IT room wall and open office area wals only. OK to replace ceiling tiles
ELE19-03474 Electrical Rough-In10/7/201910/8/201910/8/2019 8:58:17 AMAPASS
electrical rough in and under ground.
Phil is the contact Phone #: ###-#### Inspection requested via web by Deb Ipsen Exterior egress lighting only ok to cover
ELE19-03833 Conference10/7/201910/8/201910/8/2019 8:41:28 AMANR
Daniel Phone #: ###-#### Was onsite at 8:40am. No body home. No answer.
ELE19-03738 Electrical Rough-In10/7/201910/8/201910/8/2019 12:00:00 AMPCANC
Contact is Brian Prussia. The install starts at 12 if the inspector can come between 2-4 that would be the best. Thank you!! Phone #: ###-#### >> Inspection requested via web by BRS Permitting