BLD96-01321
| INSP-Sprinkler Rough-in/Hydro | 10/9/1998 | 10/9/1998 | 10/9/1998 12:00:00 AM | A | FAIL |
|
|
combustibles above in corridors; head needed in bathroom; sway bracing needed; smoke detector too close to diffuser;
|
BLD96-01321
| INSP-Sprinkler Rough-in/Hydro | 10/9/1998 | 10/9/1998 | 10/9/1998 12:00:00 AM | A | FAIL |
|
|
sway bracing not done; combustibles above drop ceiling; needs head in bathroom by dressing rooms; smoke detector within 3 feet of diffuser
|
BLD97-02910
| INSP-Final Inspection | 10/8/1998 | 10/9/1998 | 10/9/1998 12:00:00 AM | A | PART |
|
|
sandra ###-#### sprinkler head overspaced by copiers
|
BLD98-01813
| INSP-Final Inspection | 10/8/1998 | 10/9/1998 | 10/9/1998 12:00:00 AM | A | PASS |
|
|
gary ###-#### occ approved; assembly permit required
|
BLD98-00926
| INSP-Final Inspection | 10/9/1998 | 10/9/1998 | 10/9/1998 12:00:00 AM | P | FAIL |
|
|
EARL ###-#### AT 5:00 PM speaker in conference rooms
|
BLD98-01586
| INSP-Final Inspection | 10/8/1998 | 10/9/1998 | 10/9/1998 12:00:00 AM | P | PASS |
|
|
Scheduled by Hello!. Contact phone is [8673521]. occ approved
|