BLD02-00023
| FIRE-Final Inspection | 10/8/2002 | 10/9/2002 | 10/9/2002 12:00:00 AM | A | FAIL |
|
|
one duct smoke detector is mounted in an enclosure but the other is not and needs to be. Contractor to provide enclosure and test detectors 10/9/2002 12:22:52 PM
|
MIS02-00228
| FIR-Final | 10/8/2002 | 10/9/2002 | 10/9/2002 12:00:00 AM | A | PART |
|
|
a temporary occupancy was given which is to last for just one week, This is to allow the contractor time to install the duct smoke detectors 10/9/2002 8:00:02 AM
|
BLD01-02961
| FIRE-Final Inspection | 10/8/2002 | 10/9/2002 | 10/9/2002 12:00:00 AM | A | FAIL |
|
|
remove thumbturn from main exit door. It can be replaced with keyed hardware, provide "door to remain unlocked during business hours" sticker over main exit, remove thumbturn and keyed hardware from the second exit, provide fire extinguisher in office building and provide current inspection tags for the existing fire extinguishers 10/9/2002 9:10:19 AM
|
BLD01-02962
| FIRE-Final Inspection | 10/8/2002 | 10/9/2002 | 10/9/2002 12:00:00 AM | A | FAIL |
|
|
remove thumbturn from main exit door. It can be replaced with keyed hardware, provide "door to remain unlocked during business hours" sticker over main exit, remove thumbturn and keyed hardware from the second exit, provide fire extinguisher in office building and provide current inspection tags for the existing fire extinguishers 10/9/2002 9:10:27 AM
|
BLD01-02963
| FIRE-Final Inspection | 10/8/2002 | 10/9/2002 | 10/9/2002 12:00:00 AM | A | FAIL |
|
|
remove thumbturn from main exit door. It can be replaced with keyed hardware, provide "door to remain unlocked during business hours" sticker over main exit, remove thumbturn and keyed hardware from the second exit, provide fire extinguisher in office building and provide current inspection tags for the existing fire extinguishers 10/9/2002 9:10:33 AM
|
FIR02-00387
| INSP-Final Inspection | 10/9/2002 | 10/9/2002 | 10/9/2002 12:00:00 AM | P | PASS |
|
|
fire sprinklers finaled 10/9/2002 2:37:16 PM
|
FIR02-00379
| INSP-Final Inspection | 10/9/2002 | 10/9/2002 | 10/9/2002 12:00:00 AM | P | PASS |
|
|
fire sprinklers finaled 10/9/2002 3:07:36 PM
|
BLD02-01970
| FIRE-Final Inspection | 10/9/2002 | 10/9/2002 | 10/9/2002 12:00:00 AM | P | PASS |
|
|
fire life/safety finaled
|
BLD02-01478
| FIRE-Final Inspection | 10/8/2002 | 10/9/2002 | 10/9/2002 12:00:00 AM | P | PASS |
|
|
fire life/safety finaled 10/9/2002 10:51:40 AM
|