Inspections for the day of: Thursday, October 9, 2003.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00547 INSP-Final Inspection10/8/200310/9/200310/9/2003 12:00:00 AMAFAIL
BRUCE; Phone #: ###-#### Internet Inspection Request from: Darla Downs sprinkler head painted; annual inspection due on sprinkler system; spare heads needed 10/9/2003 10:30:02 AM
BLD02-02569 FIRE-Final Inspection10/8/200310/9/200310/9/2003 12:00:00 AMAFAIL
LYNN; Phone #: ###-#### Internet Inspection Request from: Darla Downs resubmittals are needed to show change in rack height for the racks on the north wall 10/9/2003 11:00:27 AM
BLD03-00430 FIRE-Conference10/9/200310/9/200310/9/2003 12:00:00 AMAPART
met with tenenat and reviewed plans - will need keyed main exit and rear exit with lever hardware; repair exit signs; extinguishers needed; test extinguishing system; tie extinguishing system to alarm panel (plans required); see fire sprinkler permit for other items
FIR03-00603 INSP-Sprinkler Rough-in10/9/200310/9/200310/9/2003 12:00:00 AMPPART
underground--mick - ###-#### uG okay to cover; will need to flush and hydro 10/9/2003 4:24:25 PM
FIR03-00535 INSP-Final Inspection10/8/200310/9/200310/9/2003 12:00:00 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Teresa Costello need additional map at FACP as annunciator is located at different address for dispatch address; sprinkler head too close to hood in kitchen 10/9/2003 4:26:00 PM
FIR03-00427 INSP-Final Inspection10/8/200310/9/200310/9/2003 12:00:00 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Robert Bailey NAC circuits aren't wired as shown on plans; need map with initiating devices; damper #2 detector dirty; NFPA 72 record of completion; 10/9/2003 4:35:02 PM
BLD02-00090 FIRE-Final Inspection10/9/200310/9/200310/9/2003 12:00:00 AMPPART
john; Phone #: ###-#### Internet Inspection Request from: Darla Downs tested elevator lobby doors for release with fire alarm and that is okay but doors don't remain latched as strike is released on fire; fire doors to remain latched but release lock 10/9/2003 4:36:41 PM
BLD02-02759 FIRE-Final Inspection10/9/200310/9/200310/9/2003 12:00:00 AMPFAIL
###-#### jeff extinguishers and fire alarm system is not required but has local alarm system with pulls and one pull is needed at south exit 10/9/2003 1:10:00 PM
BLD03-01105 FIRE-Final Inspection10/9/200310/9/200310/9/2003 12:00:00 AMPFAIL
###-#### jeff###-#### jeff extinguishers and fire alarm system is not required but has local alarm system with pulls and one pull is needed at south exit 10/9/2003 1:10:13 PM
BLD03-02002 FIRE-Final Inspection10/9/200310/9/200310/9/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/9/2003 at 9:47:10 AM. Contact: ###-####.