ELE05-03806
| ELE-Aging Inspection | 10/9/2006 | 10/9/2006 | 10/9/2006 4:51:56 PM | | DONE |
|
|
suc
|
ELE06-00802
| ELE-Aging Inspection | 10/9/2006 | 10/9/2006 | 10/9/2006 4:51:31 PM | | DONE |
|
|
no sign yet
|
ELE06-01085
| ELE-Aging Inspection | 10/9/2006 | 10/9/2006 | 10/9/2006 4:40:27 PM | | NR |
|
|
suc
|
ELE06-01486
| Final | 10/9/2006 | 10/9/2006 | 10/9/2006 4:38:26 PM | P | PASS |
|
|
house will be left open for inspection Internet Inspection Request from: Cevyn Recla ok to final
|
ELE06-03261
| Final | 10/9/2006 | 10/9/2006 | 10/9/2006 3:56:17 PM | P | PASS |
|
|
Brian; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final, signed occ card
|
ELE06-03693
| Permanent Service | 10/9/2006 | 10/9/2006 | 10/9/2006 3:15:42 PM | P | PASS |
|
|
wayne Note: please call to meet with; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s exst meter pak n ok
|
ELE06-03220
| Electrical Rough-In | 10/9/2006 | 10/9/2006 | 10/9/2006 2:50:50 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/9/2006 at 7:52:50 AM. Contact: ###-####. walls only ok to cover
|
ELE06-03598
| Permanent Service | 10/9/2006 | 10/9/2006 | 10/9/2006 1:47:37 PM | P | FAIL |
|
|
bob; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, corr not made, no address
|
ELE06-03683
| Electrical Rough-In | 10/9/2006 | 10/9/2006 | 10/9/2006 1:17:44 PM | P | FAIL |
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.3(B) listed equipment shall be used in accordance with mfgr's instructions (breakers), BCC job id shall be posted, all underground shall be inspected prior to cover
|
ELE06-01925
| Final | 10/9/2006 | 10/9/2006 | 10/9/2006 12:11:57 PM | P | PASS |
|
|
Ramiz; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
|
ELE06-03717
| Final | 10/6/2006 | 10/9/2006 | 10/9/2006 12:11:28 PM | A | PASS |
|
|
Shane; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
|
ELE06-02513
| Electrical Rough-In | 10/9/2006 | 10/9/2006 | 10/9/2006 12:11:19 PM | P | PART |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles electrode ok for dirt cover no access to house called
|
ELE06-03717
| Electrical Rough-In | 10/6/2006 | 10/9/2006 | 10/9/2006 10:51:24 AM | A | PASS |
|
|
Shane; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric ok
|
ELE06-02672
| Electrical Rough-In | 10/6/2006 | 10/9/2006 | 10/9/2006 10:48:07 AM | A | PASS |
|
|
Work performed by Matthew White.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz called contr about bkr label,faceplates, fan sw knob, loose recpt mbr, furnace room, ric ok, will call for final, need to add sticker for service, label bkr spare
|
ELE06-01612
| Final | 10/9/2006 | 10/9/2006 | 10/9/2006 10:03:30 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams called to put on permanent sticker for house panel, corr made, ok to final
|
ELE06-02068
| Final | 10/6/2006 | 10/9/2006 | 10/9/2006 9:45:11 AM | A | NH |
|
|
ron; Phone #: ###-#### - note: call for access code Internet Inspection Request from: Patricia Smith called for code, would not work, will recall
|
ELE06-03684
| Rough-In Permanent Service | 10/6/2006 | 10/9/2006 | 10/9/2006 9:26:06 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: William Zerfas ric ok, p/s u/g n ok
|
ELE06-00976
| Electrical Rough-In | 10/6/2006 | 10/9/2006 | 10/9/2006 8:59:05 AM | A | PASS |
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told owner to make-up smoke detectors, rest ok, ric ok
|
ELE06-00113
| Electrical Rough-In | 10/6/2006 | 10/9/2006 | 10/9/2006 8:13:58 AM | A | PART |
|
|
craig Note: ceiling for the pool area; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ceiling pool area ok to cover anop
|
ELE06-02464
| Final | 10/9/2006 | 10/9/2006 | 10/9/2006 8:13:03 AM | A | PASS |
|
|
ok to final, should have done rather than part, talked to contr, said would fix
|
ELE06-03513
| Electrical Rough-In | 10/6/2006 | 10/9/2006 | 10/6/2006 4:02:56 PM | A | CANC |
|
|
UNDERGROUND INSPECTION - PAUL KLINDT; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|