Inspections for the day of: Tuesday, October 9, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00706 INSP-Conference10/9/200710/9/200710/9/2007 3:25:45 PMPDONE
Conference to discuss access control egress door interconnection to the fire alarm panel.
BLD07-01414 FIRE-Final Inspection10/9/200710/9/200710/9/2007 3:17:22 PMPPASS
Life safety inspection passed.
FIR07-00441 INSP-Alarm Testing10/5/200710/9/200710/9/2007 3:16:30 PMADEFR
sandy Note:elevator Phone #: ###-####
Can be completed in conjunction with the remainder of the fire alarm work to be inspected ie. cleanroom areas.
BLD07-02025 FIRE-Final Inspection10/3/200710/9/200710/9/2007 2:36:00 PMAPASS
C/N completed, fire life safety inspection passed.
FIR07-00693 INSP-Final Inspection10/3/200710/9/200710/9/2007 2:24:21 PMAPASS
Corrections are complete, final alarm inspection passed, permit finaled, need NFPA 72 forms for signature at next site visit.
BLD05-03448 FIRE-Final Inspection10/8/200710/9/200710/9/2007 12:27:09 PMAPASS
Fire life safety finaled.
FIR06-00045 INSP-Final Inspection10/8/200710/9/200710/9/2007 12:25:59 PMAPASS
Permit finaled.
FIR07-00323 FIR-Aging Inspection10/9/200710/9/200710/9/2007 12:15:18 PM DEFR
wip
BLD07-01239 FIRE-Final Inspection10/8/200710/9/200710/9/2007 12:11:35 PMAFAIL
Need shell permit final prior to TI finals, provide one additional PFE as discussed and per plan review annotations, provide approved door hardware at the second exit pair of doors south side, need to final project related fire sprinkler permit. NOTE: Tenant has occupied this space prior to the issuance of a certificate of occupancy.
BLD07-00349 FIRE-Final Inspection10/8/200710/9/200710/9/2007 12:06:42 PMAFAIL
Missing fire dept. access marking, need to final fire sprinkler permit, need to provide dust control at the vicinity of the FACP as promised.
FIR07-00425 INSP-Sprinkler Rough-in/Hydro10/8/200710/9/200710/9/2007 12:03:39 PMAPART
OH hydrostatic test for the 4th floor passed.
FIR07-00694 INSP-Alarm Testing10/8/200710/9/200710/9/2007 11:12:38 AMAPART
Permit final pending PIV tamper switch, tamper at hose system, one flow switch in need of adjustment, and the flow switch at the hose system as noted on plans, remainder of fire alarm work tested satisfactory including all other zones, FACP, monitoring, etc., also need to sign record of completion forms.
FIR07-00844 INSP-Final Inspection10/9/200710/9/200710/9/2007 11:06:15 AMPPASS
Quick permit finaled.
FIR07-00844 INSP-Alarm Testing10/8/200710/9/200710/9/2007 11:05:19 AMAPASS
Fire alarm work passed inspection.
FIR07-00821 INSP-Final Inspection10/8/200710/9/200710/9/2007 11:01:21 AMAPASS
Hood suppression system operated correctly under test conditions, corrections verified for completion, need test report documentation provided at next site visit as agreed.