BLD06-00714
| FIRE-Final Inspection | 10/9/2007 | 10/9/2007 | 10/9/2007 5:54:08 PM | P | PASS |
|
|
life safety passed
|
BLD07-00428
| FIRE-Final Inspection | 10/9/2007 | 10/9/2007 | 10/9/2007 4:03:16 PM | P | PASS |
|
|
LIfe safety passed
|
BLD07-01452
| FIRE-Final Inspection | 10/9/2007 | 10/9/2007 | 10/9/2007 3:33:35 PM | P | FAIL |
|
|
The project related fire alarm is needed to be signed off first.
|
FIR07-00789
| INSP-Final Inspection | 10/9/2007 | 10/9/2007 | 10/9/2007 3:19:49 PM | P | PASS |
|
|
Permit finaled.
|
FIR07-00584
| INSP-Sprinkler Rough-in | 10/8/2007 | 10/9/2007 | 10/9/2007 3:01:39 PM | A | PASS |
|
|
Sprinkler piping is ok to cover. The sprinkler elevations in the patio areas needs addressed.
|
BLD07-01726
| FIRE-Final Inspection | 10/9/2007 | 10/9/2007 | 10/9/2007 2:59:50 PM | P | FAIL |
|
|
Repair the two exit sign/emergency lights as marked on the plans. Provide the three new emergency lights as marked on the plans. Provide a racking permit for all of the racks that are currently being installed. The extended coverage upright heads located on both sides of the two hour demising wall are obstructed by the enveloped trusses. This work requires a separate sprinkler permit. Repair the roll down fire doors in the two hour demising wall or get permision to lock them shut from the Boise Fire Dept.
|
BLD07-01053
| FIRE-Final Inspection | 10/8/2007 | 10/9/2007 | 10/9/2007 11:49:42 AM | A | PASS |
|
|
LIfe safety passed.
|
BLD07-00018
| FIRE-Final Inspection | 10/8/2007 | 10/9/2007 | 10/9/2007 11:48:44 AM | A | PASS |
|
|
Life safety passed.
|
FIR07-00654
| INSP-Alarm Testing | 10/8/2007 | 10/9/2007 | 10/9/2007 11:47:28 AM | A | FAIL |
|
|
Only three of the seven new duct smoke detectors were tested. All three were missing the foam filter on the sample tube and one was also missing the donut on the back side of the detector. All three units did shut down as required. The supervision of the new nac panel by the facp was tested and passed. The remaining duct smoke detectors need to be tested and the a/v's tested. The inspection was stopped due to the missing items and time constraints.
|
MIS07-00157
| FIR-Final | 10/8/2007 | 10/9/2007 | 10/9/2007 11:08:42 AM | A | PASS |
|
|
Life safety passed.
|
BLD07-02286
| FIRE-Final Inspection | 10/8/2007 | 10/9/2007 | 10/9/2007 10:34:49 AM | A | PASS |
|
|
life safety passed.
|