Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00395 INSP-Sprinkler Rough-in/Hydro10/9/201210/9/201210/9/2012 3:51:15 PMPPASS
OH hydro test passed for building 11
FIR12-00483 INSP-Sprinkler Rough-in/Hydro10/9/201210/9/201210/9/2012 3:29:56 PMPPASS
See the city approved plans for areas where the sprinkler piping located above the hardlids can be covered. It appears that a plan modification may be needed to show the ceiling changes.
FIR12-00494 INSP-Sprinkler Rough-in10/9/201210/9/201210/9/2012 3:07:04 PMPPASS
See the city approved plans for additional areas where sprinkler piping can be covered. Also see areas marked in blue that require corrections including the addtion of a sprinkler pendant in the window display.
FIR12-00531 INSP-Final Inspection10/8/201210/9/201210/9/2012 2:31:53 PMAPASS
Permit finaled. Tim Frost is ok with no hydro test
BLD12-01611 FIRE-Final Inspection10/8/201210/9/201210/9/2012 1:35:43 PMAFAIL
Provide city approved plans and notes for inspection. I went ahead and did a walk through and noted overspaced sprinkler pendants and that the fire extinguisher needs to be mounted.
FIR12-00532 INSP-Alarm Testing10/8/201210/9/201210/9/2012 11:51:39 AMAFAIL
Plan modifications are needed to show the actual wall and fire alarm device layout. This includes the location of the remoter annunciator and the manual pull station. Also it appears that an additional strobe will be required due to cabinent position and two smoke detectors need to be relocated away from air diffusers as discussed. No testing was performed.
FIR12-00535 INSP-Alarm Testing10/8/201210/9/201210/9/2012 11:48:01 AMAFAIL
I verified the placement of the a/v's but the contractor did not want to test until the other FIR could be tested.
FIR12-00422 INSP-Sprinkler Rough-in10/8/201210/9/201210/9/2012 10:32:54 AMAPASS
Rough-in passed. Piping is ok to cover
FIR12-00087 INSP-Final Inspection10/8/201210/9/201210/9/2012 9:48:43 AMAPASS
Permit finaled
FIR12-00078 INSP-Final Inspection10/8/201210/9/201210/9/2012 9:48:15 AMAPASS
Permit finaled
FIR12-00307 FIR-Aging Inspection10/9/201210/9/201210/9/2012 8:18:38 AM NR
Steve is scheduling these DSC inspections.
FIR12-00306 FIR-Aging Inspection10/9/201210/9/201210/9/2012 8:18:08 AM NR
Steve is scheduling these DSC inspections.