ELE10-00276
| ELE-Aging Inspection | 10/9/2013 | 10/9/2013 | 10/9/2013 3:45:38 PM | | DONE |
|
|
Waiting on owner
|
GCE13-00159
| GCE-Rough-In | 10/9/2013 | 10/9/2013 | 10/9/2013 3:34:00 PM | P | PASS |
|
|
larry ###-#### Rough in ok cover p/s u/g n ok
|
ELE13-02800
| Electrical Rough-In | 10/9/2013 | 10/9/2013 | 10/9/2013 2:45:27 PM | P | PASS |
|
|
Underground for Fuel system located on the exterior of building Phone #: ###-#### >> Inspection requested via web by Stan Woodward From around dispencing area towards building. Underground rough in ok cover
|
ELE13-01954
| Final | 10/8/2013 | 10/9/2013 | 10/9/2013 2:12:02 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman 314.27(C)- Floor boxes shall be specifically listed for this application. 210.52- Up yelow bedroom. Recepticals shall be install such that no point measured horizontally along floor line in any wall space is more than 6' from a receptical outlet. 410.16(C)- basement closet. Luminaires installed in closet ceiling shall have a minimum clearence of 12" for incandescent.
|
ELE13-02488
| Electrical Rough-In | 10/9/2013 | 10/9/2013 | 10/9/2013 1:20:55 PM | P | PASS |
|
|
please call Chet at ###-#### 30 minutes befor heading to the house for access into the house please. Thank you Phone #: ###-#### >> Inspection requested via web by Jay Symonds Basement rough in ok cover
|
ELE13-02607
| Electrical Rough-In | 10/8/2013 | 10/9/2013 | 10/9/2013 12:39:59 PM | A | PASS |
|
|
Bonding and pool light potting insepction please-Kevin Phone #: ###-#### Rough in ok cover
|
GCE13-00162
| GCE-Rough-In Permanent Service | 10/9/2013 | 10/9/2013 | 10/9/2013 11:54:48 AM | P | PASS |
|
|
Bldg #200 unit 1 &2. Rough in ok cover p/s u/g n ok 2 meters required
|
GCE13-00161
| GCE-Permanent Service | 10/9/2013 | 10/9/2013 | 10/9/2013 11:53:37 AM | P | PASS |
|
|
Jim ###-#### unit 1 &2. p/s u/g n ok 2 meters required
|
GCE13-00161
| GCE-Rough-In | 10/8/2013 | 10/9/2013 | 10/9/2013 11:52:03 AM | A | PASS |
|
|
Jim ###-#### unit 1 &2. Rough in ok cover
|
ELE13-02313
| Electrical Rough-In | 10/8/2013 | 10/9/2013 | 10/9/2013 10:20:59 AM | A | FAIL |
|
|
partial ceiling Phone #: ###-#### >> Inspection requested via web by kendall bender BCC 4-10-32- Code violation not to be retained, NEC 300.11- Cables and raceways shall not be supported by ceiling grid. 800.25- Abandoned cables shall be removed or tagged for future use. 800.133- Raceways shall not be used as support for communication cables
|
ELE13-02810
| Electrical Rough-In | 10/8/2013 | 10/9/2013 | 10/9/2013 8:52:02 AM | A | PASS |
|
|
This is an inspect for the uffer ground. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Rough in ok cover
|
ELE13-02548
| Final | 10/9/2013 | 10/9/2013 | 10/9/2013 8:31:59 AM | A | PASS |
|
|
It will be open Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser Final ok
|