Inspections for the day of: Wednesday, October 9, 2013.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00497 INSP-Sprinkler Rough-in10/9/201310/9/201310/9/2013 3:44:33 PMPPASS
See the city approved plans for piping above hardlids that can be covered. Marked "ok" in red.
FIR13-00383 INSP-Sprinkler Rough-in10/9/201310/9/201310/9/2013 3:35:06 PMPPART
In general the rough-in passed. Noted missing retaining straps and a couple of earth quake braces. As-builts will be needed showing the changes in the main routing near the riser and the deletion of one of the 2" branchlines.
FIR12-00695 INSP-Sprinkler Rough-in/Hydro10/8/201310/9/201310/9/2013 2:22:34 PMAPASS
Overhead hydro passed
FIR13-00427 INSP-Sprinkler Rough-in10/8/201310/9/201310/9/2013 2:21:56 PMAPASS
Piping above hard lid is ok to cover.