Inspections for the day of: Thursday, October 9, 2014.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00534 INSP-Sprinkler Rough-in10/9/201410/9/201410/9/2014 3:36:59 PMPPASS
Rough-in passed. Piping can not be covered until a tenting inspection has been passed
FIR14-00552 INSP-Supply line flush10/9/201410/9/201410/9/2014 3:15:51 PMPPASS
UG flush passed
BLD13-02019 FIRE-Final Inspection10/7/201410/9/201410/9/2014 2:03:06 PMACANC
cancel per John Phone #: ###-####
FIR14-00464 INSP-Sprinkler Rough-in/Hydro10/8/201410/9/201410/9/2014 12:52:33 PMAPART
Overhead hydro tests passed. Piping, as installed/rough-in passed. But routeing and fitting counts have changed and per the review notes any modifications will require resubmittals. So prior to an approval for cover being given I need plan modifications and a tenting inspection.
FIR14-00461 INSP-Final Inspection10/9/201410/9/201410/9/2014 12:50:24 PMPPASS
Permit finaled
FIR14-00581 INSP-Sprinkler Rough-in10/8/201410/9/201410/9/2014 12:50:05 PMAPART
Todays inspection was for a rough-in for the second and third floors. Rough-in passed. Two locations are marked where heads have not been installed yet. Third floor piping is ok to cover. First, second and the stairwells can not be covered until insulation/filling has been verified.
BLD14-01507 FIRE-Final Inspection10/8/201410/9/201410/9/2014 11:35:38 AMAPASS
life safety passed
BLD14-02913 FIRE-Final Inspection10/8/201410/9/201410/9/2014 11:33:07 AMAFAIL
Provide revised floor plan to plan review, provide sticker at the main exit, remove the deadbolts/thumbturn from the exit doors and provide single action hardware. The main exit is ok to be keyed.
BLD14-02366 FIRE-Final Inspection10/8/201410/9/201410/8/2014 3:30:58 PMAPART
A temporary occupancy is approved with Scott's permission until the door hardware issue is worked out between the plan reviewer and the architect.