ELE17-03377
| Electrical Rough-In | 10/6/2017 | 10/9/2017 | 10/9/2017 3:16:33 PM | P | PASS |
|
|
Underground conduit. Site Contact is Kim ###-#### Phone #: ###-#### Inspection requested via web by Steve Blackmer Underground to refeed propane dispenser and sign rough in ok cover
|
ELE17-03193
| Conference | 10/7/2017 | 10/9/2017 | 10/9/2017 2:50:10 PM | P | DONE |
|
|
Introduction and review underground prep work for stand by generator instalation, trenching ; electrical conduit rough-in work Phone #: ###-#### Inspection requested via web by Carl Pelletier Discussed generator location shall have a min of depth of 36" for work space at generator disconnect. Sch.80 required where emerge from grade, grounding electrode system for each service all that needed, equipment grounds to generator each with common neutral blocks. Main disconnect for shop to remain inside and house to remain outside. Check for removal of main bonding jumper at generator in future. Will call for underground to house when ready.
|
ELE17-03193
| Electrical Rough-In | 10/9/2017 | 10/9/2017 | 10/9/2017 2:40:31 PM | P | PASS |
|
|
Introduction and review underground prep work for stand by generator instalation, trenching ; electrical conduit rough-in work Phone #: ###-#### Inspection requested via web by Carl Pelletier Partial underground from generator to shop and corner of shop headed to house rough in ok cover
|
ELE17-03392
| Permanent Service | 10/8/2017 | 10/9/2017 | 10/9/2017 1:56:06 PM | P | PASS |
|
|
Repairing damaged service due to falling tree limb. Please call ahead to make sure we are ready. Thanks Mark Phone #: ###-#### Inspection requested via web by Mark Morgan Mast replacement due to damage, rest to stay as is. Less than 6 throws at time of inspection. p/s o/h rec ok
|
ELE17-03392
| Final | 10/9/2017 | 10/9/2017 | 10/9/2017 1:55:58 PM | P | PASS |
|
|
Repairing damaged service due to falling tree limb. Please call ahead to make sure we are ready. Thanks Mark Phone #: ###-#### Inspection requested via web by Mark Morgan Final ok
|
ELE17-03394
| Final | 10/9/2017 | 10/9/2017 | 10/9/2017 1:36:46 PM | P | PASS |
|
|
Get in through back receiving door. Work is in gallery 2 Phone #: ###-#### Inspection requested via web by Randy Fletcher Final ok
|
ELE17-03394
| Electrical Rough-In | 10/9/2017 | 10/9/2017 | 10/9/2017 1:36:38 PM | P | PASS |
|
|
Get in through back receiving door. Work is in gallery 2 Phone #: ###-#### Inspection requested via web by Randy Fletcher Not part of work for BLD15-02554. Rough in of 2 30 amp 208 volt receptacle outlets located and mounted to open ceiling track for temp wiring of new displays. Rough in ok
|
ELE13-03038
| Final | 10/9/2017 | 10/9/2017 | 10/9/2017 12:50:33 PM | P | PASS |
|
|
Aging Permit clean up Phone #: ###-#### Inspection requested via web by Steve VanWinkle Final ok
|
ELE13-03038
| Electrical Rough-In | 10/9/2017 | 10/9/2017 | 10/9/2017 12:50:32 PM | P | PASS |
|
|
Aging Permit clean up Phone #: ###-#### Inspection requested via web by Steve VanWinkle listing confirmed. Rough in ok
|
ELE17-03347
| Final | 10/4/2017 | 10/9/2017 | 10/9/2017 9:54:19 AM | A | NH |
|
|
Phone #: ###-#### Inspection requested via web by sam petterson Unable to gain access. Called contractor and they called and did not get an answer. Will reschedule when someone is available.
|
ELE17-02384
| Electrical Rough-In | 10/6/2017 | 10/9/2017 | 10/9/2017 9:20:48 AM | A | PASS |
|
|
Listing inspection for panel and inverters. Rooftop crew will be onsite. Phone #: ###-#### Inspection requested via web by Ryan King Listing confirmed. Rough in ok
|