Inspections for the day of: Monday, October 9, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03377 Electrical Rough-In10/6/201710/9/201710/9/2017 3:16:33 PMPPASS
Underground conduit. Site Contact is Kim ###-#### Phone #: ###-#### Inspection requested via web by Steve Blackmer
Underground to refeed propane dispenser and sign rough in ok cover
ELE17-03193 Conference10/7/201710/9/201710/9/2017 2:50:10 PMPDONE
Introduction and review underground prep work for stand by generator instalation, trenching ; electrical conduit rough-in work Phone #: ###-#### Inspection requested via web by Carl Pelletier
Discussed generator location shall have a min of depth of 36" for work space at generator disconnect. Sch.80 required where emerge from grade, grounding electrode system for each service all that needed, equipment grounds to generator each with common neutral blocks. Main disconnect for shop to remain inside and house to remain outside. Check for removal of main bonding jumper at generator in future. Will call for underground to house when ready.
ELE17-03193 Electrical Rough-In10/9/201710/9/201710/9/2017 2:40:31 PMPPASS
Introduction and review underground prep work for stand by generator instalation, trenching ; electrical conduit rough-in work Phone #: ###-#### Inspection requested via web by Carl Pelletier
Partial underground from generator to shop and corner of shop headed to house rough in ok cover
ELE17-03392 Permanent Service10/8/201710/9/201710/9/2017 1:56:06 PMPPASS
Repairing damaged service due to falling tree limb. Please call ahead to make sure we are ready. Thanks Mark Phone #: ###-#### Inspection requested via web by Mark Morgan
Mast replacement due to damage, rest to stay as is. Less than 6 throws at time of inspection. p/s o/h rec ok
ELE17-03392 Final10/9/201710/9/201710/9/2017 1:55:58 PMPPASS
Repairing damaged service due to falling tree limb. Please call ahead to make sure we are ready. Thanks Mark Phone #: ###-#### Inspection requested via web by Mark Morgan Final ok
ELE17-03394 Final10/9/201710/9/201710/9/2017 1:36:46 PMPPASS
Get in through back receiving door. Work is in gallery 2 Phone #: ###-#### Inspection requested via web by Randy Fletcher Final ok
ELE17-03394 Electrical Rough-In10/9/201710/9/201710/9/2017 1:36:38 PMPPASS
Get in through back receiving door. Work is in gallery 2 Phone #: ###-#### Inspection requested via web by Randy Fletcher
Not part of work for BLD15-02554. Rough in of 2 30 amp 208 volt receptacle outlets located and mounted to open ceiling track for temp wiring of new displays. Rough in ok
ELE13-03038 Final10/9/201710/9/201710/9/2017 12:50:33 PMPPASS
Aging Permit clean up Phone #: ###-#### Inspection requested via web by Steve VanWinkle Final ok
ELE13-03038 Electrical Rough-In10/9/201710/9/201710/9/2017 12:50:32 PMPPASS
Aging Permit clean up Phone #: ###-#### Inspection requested via web by Steve VanWinkle
listing confirmed. Rough in ok
ELE17-03347 Final10/4/201710/9/201710/9/2017 9:54:19 AMANH
Phone #: ###-#### Inspection requested via web by sam petterson
Unable to gain access. Called contractor and they called and did not get an answer. Will reschedule when someone is available.
ELE17-02384 Electrical Rough-In10/6/201710/9/201710/9/2017 9:20:48 AMAPASS
Listing inspection for panel and inverters. Rooftop crew will be onsite. Phone #: ###-#### Inspection requested via web by Ryan King
Listing confirmed. Rough in ok