Inspections for the day of: Wednesday, October 9, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02434 ELE-Aging Inspection10/9/201910/9/201910/11/2019 3:05:39 PM FAIL
No response from previous attemps.
Doc expired
ELE19-02906 Final10/9/201910/9/201910/9/2019 2:57:18 PMPFAIL
Phone #: ###-#### Inspection requested via web by Jim Williams
300.15 All boxes shall be covered. East show window receptacle, and light 15' in not in.
440.6- Over current protection shall not exceed value on name plate. 45 max 50 amp installed.
ELE19-01226 Electrical Rough-In10/8/201910/9/201910/9/2019 2:41:32 PMPPASS
Units one and five Phone #: ###-#### Inspection requested via web by Garrett Collins Units noted rough in ok cover
ELE19-03602 Electrical Rough-In10/9/201910/9/201910/9/2019 1:30:35 PMPPASS
Shane Phone #: ###-####
Called Gemma and had ELE attached to BLD19-03611.
Discussed if existing service can remain as is during remodel. Electrical engineer spec'ed out a service change for building. I am required to enforce electrical engineer drawings as approved by plan review. The print will required to be changed by electrical engineer documenting service is ok to remain as originally installed. As per Daryl DeGrange as noted above if engineer approves service ok to remain as is.
Floor boxes and conduits rough in ok cover
ELE19-03751 Rough-In Permanent Service10/7/201910/9/201910/9/2019 11:26:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Alan Lusk
314.17(B)- Where NM cable enters a hole in a metal box or cover it shall be protected from abrasion. Fireplace, no bushing on 14-2 entering box.
408.7- Unused breaker spaces shall be closed by approved means
ELE19-02801 Final10/8/201910/9/201910/9/2019 10:48:58 AMAPASS
Garage code 1957 Phone #: ###-#### Inspection requested via web by Therrin Robertson Final ok
ELE18-03962 Final10/8/201910/9/201910/9/2019 10:48:29 AMAFAIL
Phone #: ###-#### Inspection requested via web by Therrin Robertson
210.8(A)- All bathroom receptacle outlets shall have GFCI protection.
ELE19-03496 Temporary Service10/8/201910/9/201910/9/2019 9:57:59 AMAPASS
Contact electrician on-site Shawn Evins.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek t/s u/g n ok
ELE19-03729 Rough-In Permanent Service10/8/201910/9/201910/9/2019 9:21:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok